blueplanet Operating and Installation Instructions 1502x - 2502x

Page 31

Installation and Start-Up

(A) Grid Connection

AC-connection
(see Figure 23)

Figure 21: Connection of the blueplanet 1502x

AC-connection
(see Figure 23)

Figure 22: Connection of the blueplanet 1502x

L N PE

N L1 L2 PE

Figure 23: AC-connection

AC Connections are a 3 or 4 wire connection. In 4 wire systems
incorporating a Neutral there will be the following connections;
Line-1, Line-2, Neutral, and Ground. In 3 wire systems not
incorporating a Neutral there will be the following connections;
Line-1, Line-2, and Ground.

We recommend the following conductor cross-sections for
cable lengths up to 60 feet:

– blueplanet 1502x:

up to AWG 10
75°C Copper Wire

– blueplanet 2502x:

up to AWG 10
75°C Copper Wire

Larger cross-sections should be used for longer leads.

NOTE

Use Copper Conductors only.

The following AC over-current protection must be used for the
installation of the inverter.

– blueplanet 1502x

15 A Breaker

– blueplanet 2502x

20 A Breaker

!

DANGER

Risk of electric shock at live connections.
Check that the power lead is voltage-free before
inserting it into the inverter.

!

WARNING

To reduce the risk of fi re, connect only to a circuit
provided with the required branch-circuit overcur-
rent device sized in accordance with the National
Electrical Code, ANSI/NFPA 70. The maximum size
overcurrent device shall not be more than 15 A for
the 1502x, 20 A for the 2502x.