Installation

Operating instructions for blueplanet-gridsave eco_EN

Page 23

Authorised electrician

7.2.1 Connecting grounding

The bidirectional battery inverter must be grounded to the earth system of the installation.

The cross-section of the copper wire must be at least the same cross-section of the connected outer conductor, and

at least 6 mm².

Please refer to local regulations for more information on the size of the ground cable.
Ground the device by connecting the protective earth conductor from a suitable location (e.g. main earthing bar) to

the ground terminal of the device. The bidirectional battery inverter is suitable for earthing systems.

7.2.2 Connecting the battery

Shunt1 A

Shunt1 B

Temp

gridsave eco

Battery

S+

Mid

S-

B+

B-

Main battery

isolator

Battery measurement /

precharge isolator

*
*

Figure 12: Battery connection diagram
* Connect S+ and S- cables to the battery poles for voltage measurement.

NOTE

The wiring diagrams do not show the overcurrent protective devices!
Both the main battery cables and for battery measurement / precharging, an overcurrent protective

device is recommended that is able to act as an isolator switch to shut down the device in the event

of a fault or for maintenance purposes (available as additional accessories).

NOTE

The DC cables must be permanently connected and no plug-and-socket connections are permitted!

›

Disconnecting the cable during operation may cause arcing which can cause equipment damage

or injuries.

›

When disconnecting the cables, always first ensure that device is shut down, cables B+ and B- are

disconnected, followed by the sense/precharge cables. Connections are made in the reverse order.