Configuration and Operation

Page 36

Operating instructions for blueplanet-gridsave eco_EN

8.3.6 Changing the configuration

To change the system setting, the following steps are recommended:
• Save existing configuration file.
• Change the minimum set of parameters in each case, then check that the anticipated results occur.
• Save new configuration file.

8.3.6.1 Reset to factory defaults

CAUTION

Destruction of the components due to incorrect configuration.
Operation with a different configuration for the battery module or the entire system causes damage

to the batteries or other components.

After resetting the device to factory settings, it must be configured again.

Restore factory settings for off-grid operation with voltage control – with the default voltage settings for

flooded battery or sealed battery

"

Switch the device to no-load mode with a long press of the ON button.

»

The power mode display goes off!

"

Press the alarm button and generator button simultaneously.

»

All status displays go off.

"

Press the additional "Inverter" button to select the battery type.

Green = closed battery (liquid electrolyte, flooded batteries)

Red = sealed battery = closed battery (solidified electrolyte, sealed batteries)

Off = factory settings are not reset and no settings are changed.

"

After releasing the buttons, wait for another 10 seconds until the display no longer changes.

"

Factory settings have been restored depending on the selection of flooded or sealed batteries.

8.3.6.2 Operation without generator current

NOTE

The power supply of the internal electronics of the device is provided via the DC side (battery).

In the event of heavy battery discharge, starting is only carried out via charging.

Protect batteries if the generator is not present:
1. Switch on Econo mode.

»

The device issues a pulsing output voltage and only supplies continuous voltage if the limit value is exceeded.

This charges the battery with renewable energy.

2. Switch the device to Econo mode as often as possible to protect the battery against discharge.

»

The protective function against deep discharge can be disabled briefly, however.

DANGER! The DC cables are still live.

"

Ensure that there is no voltage present on the grid connection terminals.