1 display of status and fault messages – KACO blueplanet gridsave eco 5.0 TR1 User Manual

Page 29

Advertising
background image

Configuration and Operation

Operating instructions for blueplanet-gridsave eco_EN

Page 29

8.1.1 Display of status and fault messages

Item Meaning

LED

Status

Description

1

Generator

status

Status LED displays generator operation:

No generator control

Generator starting

Generator running

Generator cannot start automatically

Generator fault



Off
Green flash-

ing green

Yellow flash-

ing

Red flashing

2

AC source

Blue

Input of external alternating voltage from

generator or

power grid

3

Transfer

Off

Blue

Alternating voltage outside tolerance range for synchronisation
External alternating voltage connected to AC load output.

(The status LED flickering is normal)

4

Consumer (AC

load)

Blue

Consumers are supplied with AC voltage. (Display also possible

without DC connection on the device)

5

Power mode

Status LED displays device operation:

Device in no-load operation. Monitoring and data acquisition

active

Device is active in save mode and measures the load condi-

tions

Green
Slow flashing

in green

Fast flashing

in green

Device is preparing to start.

Green

Red flashing

Device is switched on

Interrupted power circuit or poor battery connection > no out-

put of inverter power possible

Red

Fault detected

6

Export

Green

Energy is exported to the grid with on-grid plant

Flashing in

green

AC load is supplied

7

Battery status

Display of the battery voltage (standard) or charge status.
With active SoC control, the proportion of usable residual charge

in the batteries is displayed. The usable charge is between 100 %

SoC and the shutdown SoC.

upper

range

Green

Display of the trickle voltage or higher voltage

Red

Immediate shutdown due to high DC voltage

lower

range

Yellow

Battery weak

Red flashing

Immediate shutdown due to low DC voltage

Red

Shutdown due to weak battery

Show all

Red flashing

Shutdown if low battery voltage is removed !

In the case of an emergency, the operation of the device can

be maintained at reduced power via the battery shutdown

limit through to complete discharge.

This emergency function may damage the battery and the

connected devices, however!