4 starting and stopping the generator – Magnum Energy ME-RTR Router User Manual

Page 103

Advertising
background image

Page 95

©

2014 Magnum Energy, Inc.

Using an AGS Module: Operation

To manually start the generator and have it automatically stop:
From the AGS Home screen (to access, refer to Section 7.1.1.1):
1. Press the CTRL button.
2. Turn the SELECT knob to the 03 Gen Control menu.
3. Press the SELECT knob. The Set Gen Control menu displays with an arrow to the right of the

current setting.

4. Turn and press the SELECT knob to select the ON setting. The selection arrow appears to the

right of the screen. The generator should start at this time.

After the generator is running, rotate the SELECT knob to AUTO (under the CTRL: 03 Gen Control

menu), and then press the SELECT knob to select the AUTO setting.
Note: When the generator is manually started, and then changed to autostop, the SETUP: 04A

Gen Run DC Volts stop settings are used to determine when the generator will autostop. If the

SETUP: 04A Gen Run VDC is set to OFF, the Start/Stop Delay and Stop Volts values that were

entered prior to selecting OFF will still be used to autostop the generator.
If the generator does not start or stop as expected, refer to Section 7.3.

To manually start the generator:
From the AGS Home screen (to access, refer to Section 7.1.1.1):
1. Press the CTRL button.
2. Turn the SELECT knob to the 03 Gen Control menu.
3. Press the SELECT knob. The Set Gen Control menu displays with an arrow to the right of the

current setting.

4. Turn and press the SELECT knob to select the ON setting. The selection arrow appears to the

right of the screen. The generator should start at this time.

If the generator does not start as expected, refer to

Section 7.3.

To manually stop the generator:
From the AGS Home screen (to access, refer to Section 7.1.1.1):
1. Press the CTRL button.
2. Turn the SELECT knob to the 03 Gen Control menu.
3. Press the SELECT knob. The Set Gen Control menu displays with an arrow to the right of the

current setting.

4. Turn and press the SELECT knob to select the OFF setting. The selection arrow appears to the

right of the screen. The generator should stop at this time.

If the generator does not stop as expected, refer to Section 7.3.

7.2.4

Starting and Stopping the Generator

The generator can be manually started/stopped, as well as autostarted/autostopped using the

available settings from your ME-RTR.
To autostart/autostop the generator:
In order for the generator to autostart/autostop, one or more of the following autostart/autostop

conditions must be pre-set (see Section 7.1):

Autostart Conditions
• 04A Gen Run DC Volts (pp. 79-81)
• 04B Gen Run Time (p. 81)
• 04C Gen Run AC Amps (pp. 81-82)
• 04D Gen Run SOC (pp. 82-83)
• 04E Gen Run Temp (pp. 83-84)
• 04H Gen Exercise (pp. 87-88)
• 04J Gen 100% SOC (pp. 89-90)

Autostop Conditions
• 04A Gen Run DC Volts (pp. 79-81)
• 04B Gen Run Time (p. 81)
• 04C Gen Run AC Amps (pp. 81-82)
• 04D Gen Run SOC (pp. 82-83)
• 04E Gen Run Temp (pp. 83-84)
• 04F Max Gen Run Time (p. 85)
• 04G Gen Quiet Time (pp. 85-86)
• 04H Gen Exercise (pp. 87-88)