Appendix B – Compatibility Matrix

Page 120

Button

FEATURES/SETTINGS

Model/

Level

Required

Default

Setting

Main

Menu

Menu

Heading/Item

Selections/

Adjustments Range

SETUP

04 AGS

Setup

04A Gen Run DC

Volts

OFF, Start Volts= 9.0-15.9*

≥Level 1

11.5V

Start Delay= 0-127s, 1-127m

120 Secs

Stop Volts= 9.1-16.0*, Float

14.4V

Stop Delay= 0-127s, 1-127m

120 Secs

04B Gen Run Time

OFF, Start = 12:00A-11:45P

≥Level 1

OFF

Stop Daily = 12:00A-11:45P

12:00A

04C Gen Run AC

Amps

Start AC Amps = OFF, 5-60A

≥Level 4

OFF

Stop AC Amps = 4-59A

4A

Start Delay = 0-127s, 1-127m

120 sec

Stop Delay = 0-127s, 1-127m

120 sec

04D Gen Run SOC

OFF, Start SOC = 20-99%

≥Level 1

[6]

OFF

Stop SOC = 21-100%

90%

04E Gen Run Temp

Start = OFF, ExtInput, 65-95F

(18-35C)

≥Level 1

OFF

Time = 0.5-25.5 Hrs

65F/2 Hrs

04F Max Gen Run

Time

OFF, 0.1-25.5 Hrs

≥Level 1

12 Hrs

04G Gen Quiet Time

OFF, Begin = 12:00A-11:45P

≥Level 1

OFF

End Time = 12:00A-11:45P

10:00A

OFF, Topoff = 30-120 Mins

OFF

04H Gen Exercise

OFF, Days = 1-255 days

≥Level 1

OFF

Start Time = 12:00A-11:45P

8:00A

Run Time = 0.1-25.5 Hrs

1.0 Hrs

04I Gen No-Load

Time

Warm-up = 0-127s, 1-127m

≥Level 1

60 Secs

Cooldown = 0-127s, 1-127m

04J Gen 100% SOC

OFF, Days = 1-255

≥Level 1

[6]

OFF

Time = 12:00A-11:45P

8:00A

05 BMK

Setup

05A Charge Effi ciency Auto, 50-99%

≥Level 1

[6]

Auto

05B Battery AH Size

200-2500 AH

400 AH

06 Remote

Control

06A Remote Control

System, Port 1 – Port 6

≥Level 1

System

* – 12-volt values shown; multiply 12-volt values x2 for 24v systems, and x4 for 48v systems.
** – These settings return to the factory default setting when power to the router is removed.
[1] Not available on MM/MM-E/MM-AE/MMS/MMS-E Series models.
[2] AC Couple mode activates when Battery Type = Custom w/ MS-PAE Rev
≥4.1 or MS/MS-PE Rev ≥5.0.
[3] AC output volts only accurate when connected to MS, MS-PAE, MS-PE or MSH Series models.
[4] AC amps displays only appear when connected to MS-PAE, MS-PE, or MSH Series models.
[5] Level 2 and 3 inverters can be used, but: Level 2 inverters are limited from 1 to 4.5 hrs, Level 3 inverters

must be <Rev.4.1 and are limited from 1 to 6.5 hrs, Level 3 inverters must be ≥Rev4.1 (and MMS Rev 1.5)
and are limited from 1.5 to 6.5 hrs.

[6] BM/SOC features require the ME-BMK (Battery Monitor Kit) to be installed.