Using an ags module: operation, Ags setup menu continued from previous page – Magnum Energy ME-RTR Router User Manual

Page 106

Advertising
background image

©

2014 Magnum Energy, Inc.

Page 98

Using an AGS Module: Operation

Figure 7-4, AGS SETUP Menu Maps (Section 2)

Set Gen Quiet Time
Begin Quiet= OFF
End Quiet =10:00AM
P3 edit AGS SETUP

04G Gen Quiet Time
OFF

P3 View AGS SETUP

04H Gen Exercise
OFF

P3 View AGS SETUP

Set Gen Exercise

Start Gen Days =OFF
Start Time = 8:00AM

P3 edit AGS SETUP

04I Gen No-Load Time
Warm-up = 60secs
Cooldown = 60secs
P3 View AGS SETUP

P

R

P

R

Set Gen No-Load Time
Warm-up = 60secs
Cooldown = 60secs
P3 edit AGS SETUP

P

P

0.1-25.5 Hrs

AGS SETUP menu continued from previous page

R

P

Set Time to Topoff
Battery before Quiet
Time= OFF
P3 edit AGS SETUP

OFF, 12:00AM-11:45PM

OFF, 30, 60, 90,120 Mins

Set Gen Exercise

Run Time= 1.0 Hours

P3 edit AGS SETUP

0-127 secs, 1-127 mins

04J Gen 100% SOC
OFF

P3 View AGS SETUP

Set Gen 100% SOC
Start Gen Days =OFF
Start Time = 8:00AM
P3 edit AGS SETUP

P

R

Days = OFF, 1-255
Time
= 12:00AM-11:45PM

Days = OFF, 1-255
Time
= 12:00AM-11:45PM

Menu Button

Default/

Current

Setting

Press SELECT

Knob

Rotate

SELECT

Knob

LEGEND

SETUP

04A Gen Run DC Volts
Start= 23.0V/ 60secs
Stop = 28.8V/120secs
P3 View AGS SETUP

Menu Headings

Menu

Port

Display Type

R

Set Gen Run DC Volts
Start Volts = 23.0V
Stop Volts = 28.8V
P3 edit AGS SETUP

P

Device

Setting

Settings/Range

x2

x2

Advertising