AN-X2-SQD-MAS Page

17

Parameter

Keyword

Valid entries

Drop number

Drop=

1-8

Slot number

Slot=

1-16

Input Registers

InpRegs=

Number of registers, 1 to 127

Output Registers

OutRegs=

Number of registers, 1 to 127

Description

Desc=

Maximum 63 characters, enclosed in
double quotes

End of drop definition

EndDrop

Examples:

Slot=4 InpRegs=0 OutRegs=1 Desc="ROM221 16 OUT AC" ; ModType=a0

Slot=9 InpRegs=4 OutRegs=4 Desc="ROM121 4 OUT ANLG" ; ModType=82

When AN-X creates a Remote I/O configuration file after an autoconfiguration, it inserts
part numbers and descriptions from its internal module database.

Sample Remote Configuration File

;

QTS AN-X SQD MAS Auto Configuration Utility

;Copyright (c) 2012 Quest Technical Solutions

;Auto Config Sqd Mas File 4.1.3

Drop=1

Slot=2 InpRegs=1 OutRegs=0 Desc="RIM101 16 IN AC/DC" ; ModType=e0

Slot=3 InpRegs=1 OutRegs=0 Desc="RIM101 16 IN AC/DC" ; ModType=e0

Slot=4 InpRegs=1 OutRegs=0 Desc="RIM101 16 IN AC/DC" ; ModType=e0

EndDrop ; MaxSlot=4 NumInpRegs=3 NumOutRegs=0

Drop=8

Slot=2 InpRegs=0 OutRegs=1 Desc="ROM221 16 OUT AC" ; ModType=a0

Slot=3 InpRegs=0 OutRegs=1 Desc="ROM221 16 OUT AC" ; ModType=a0

Slot=4 InpRegs=0 OutRegs=1 Desc="ROM221 16 OUT AC" ; ModType=a0

Slot=9 InpRegs=0 OutRegs=4 Desc="ROM121 4 OUT ANLG" ; ModType=82

EndDrop ; MaxSlot=9 NumInpRegs=0 NumOutRegs=7