Other options and mapped data – ProSoft Technology AN-X2-SQD User Manual

Page 27

Advertising
background image

AN-X2-SQD-MAS Page

21

Example:

To map the outputs from drop 1 slot 4 to ControlLogix offset 27, add the following line
to the DataOutput section of the connection

27, d1s4

Example:

To map the inputs from the drop 3 slot 11 to the next available ControlLogix location,
add the following line to the DataInput section of the connection

, d3s11

Other Options and Mapped Data

LED Mode

To set debug mode, enter a line with the keyword LedModeDebug in the ControlLogix
configuration file. See page 40 for details.

Drop Error Table

The drop error table consists of 8 bits in one 16-bit word, one bit per drop. Bit 0
corresponds to drop 1, bit 1 corresponds to drop 2, and so on.

If a configured drop is not active on the network, the bit is 1. If a configured drop is
active on the network, the bit is 0. The bit is always 0 for an unconfigured drop.

The drop error table is automatically mapped to the first word of input data for
ControlLogix connection 0.

Diagnostic Data

In addition to the I/O data, there are other items that are automatically mapped by the
AN-X2-SQD-MAS to connection 15.

TIP

If you use connection 15 to monitor diagnostic data, set a long RPI to
reduce the Ethernet traffic, since the diagnostics do not need to be
updated as frequently as I/O data.

The items are found at the locations shown and are described in detail in the sections that
follow.

Starting Offset

Description

0

Diagnostic counters

35

UDP connection diagnostics

40

Connection 0 statistics

Advertising