background image

AN-X2-SQD-MAS Page

23

Offset

Counter

4

UDP Tx Busy

5

UDP Rx Busy

Connection Statistics

The AN-X module maintains statistics for each scheduled connection.

The statistics for each connection consists of 10 words of data. Only three words in the
ten word block are used.

Offset

Description

0

Average time for last 32 updates

2

Minimum time since the connection statistics were reset

4

Maximum time since the connection statistics were last reset

The units for the times are 0.1 milliseconds. A value of 87 means 8.7 ms.

Values update at a rate equal to 100 times the RPI for the connection. Averages are
calculated for the last 100 updates.

Resetting Connection Statistics

To reset the connection statistics, set bit 0 of output word 0 of connection 15. AN-X
resets the statistics on the transition from 0 to 1.

This does not reset the UDP diagnostics.

Example Configuration File:

;QTS AN-X SQD MAS Auto Configuration Utility

;Copyright (c) 2012 Quest Technical Solutions

;Auto Config Ethernet/IP File

ClxName Anx2SqdMas

ClxPrefix SQD_

LedModeDebug

ClxSlot 0

DataInput ; Inputs to ControlLogix

2 d1s02 ; 2->2 ( 1) "RIM101 16 IN AC/DC"

3 d1s03 ; 3->3 ( 1) "RIM101 16 IN AC/DC"

4 d1s04 ; 4->4 ( 1) "RIM101 16 IN AC/DC"

5 d8s09 ; 5->8 ( 4) "ROM121 4 OUT ANLG"