WLCA/WLHA High Wall Evaporator

piston/orifiCE instALLAtion instrUCtion

rEfriGErAnt pipinG

r

educing bushing goes here for

18,000 Btuh system match

WLH24

Any change in the diameter of the tubing
must be made at the indoor connection.

Line-set diameter is determined by the
condenser service valve size.

Use of a larger diameter liquid or suc-
tion line can harm the compressor!

Important:

Replace the existing piston (before installing the unit) with the piston

supplied in Kit Bag when any:

• WLHA24 evaporator is matched with a

S1CA8000 or S1HA8000 condenser which has

an 18,000 Btuh compressor (“8” in the capacity decoding field). The piston will need

relacement only on the 18,000 Btuh zone.*

Your EMI evaporator unit contains the appropriate piston for your model. Refer to this

document to determine if a change is required based on your condenser rating. If your

match is not listed below no piston change is required. (See chart below)

propEr instALLAtion of piston/orifiCE rEpLACEmEnt

* “8

” in the capacity decoding field = 18,000 Btuh

model #

Evaporator

Condenser

Btuh

factory installed

Piston/Orifice Size

field Changeover

Piston/Orifice Size

WLHA24

S1CA8000

.059”

.053”

WLHA24

S1HA8000

.059”

.053”

Evaporator