EMI WLHA User Manual

Page 25

Advertising
background image

www.enviromaster.com

25

WLCA/WLHA High Wall Evaporator

Note:

While in Remote thermostat

mode (see configuration), only the

“FAN” and “TIME” buttons are acti-

vated and will beep when pressed.

Memory Backup:

In the event of a power failure the control will

retain all of it’s settings including the mode

of operation. When power is restored, after

a three minute time delay, the control will re-

turn to the mode of operation that it was in

prior to the power failure.

fault Conditions

Room air sensor fault: E01

If the room air sensor is disconnected,

damaged or malfunctions the LCD display

will flash error code “E01” to signify that

a fault has occurred. Operation will con-

tinue with the control using the last known

value for the room air sensor.

sEqUEnCE of opErAtion – WALL moUntEd tHErmostAt modE

Condensate fault: E02

If the control senses a condensate fault

condition either through the optional con-

densate pumps safety switch or the drain

pan sensors, the LCD display will flash

error code “E02”. The compressor will

switch off for a minimum of three minutes

and until the fault condition is corrected.

ID coil sensor fault: E03

The indoor coil sensor monitors the tem-

perature of the indoor coil. If a freeze

condition exists continuously for three

minutes, the LCD will display error code

“E03” to signify that a fault has occurred.

The compressor will switch off for a mini-

mum of three minutes and until the fault

condition is corrected. Also, if the micro-

processor detects an evaporator freeze

condition four times within a 24 hour pe-

riod, the filter check indicator will appear.

infrArEd rEmotE ControL option

operational range 55- 90° f (in 1° increments.)

NOTE: Batteries Included.

Pressing the “+” will increase

the set point temperature setting.

Pressing the “-“ button will de-

crease the setpoint temperature

setting.

poWEr

Pressing the “poWEr” button will

turn the unit On or Off.

fAn

Pressing the “fAn” button will

place the unit in fan mode.

AUto

Pressing the “AUto” button will

place the unit in Auto changeover
mode.

fAn spEEd

Pressing the “fAn spEEd” but-

ton will scroll the unit through fan

the fan speed selection. The se-

quence is High, Low and Auto.

HEAt

Pressing the “HEAt” button will

place the unit in Heat mode.

CooL

Pressing the “COOL” button will

place the unit in Cool mode.

dry

Pressing the “DRY” button will

place the unit in Dry Mode.

LoUVEr

Pressing the “LOUVER” button

will enter the Louver Configura-
tion mode. While in Louver Con-

figuration mode, each successive

press of the louver button will scroll

through the louver positions. After

idle for 10 seconds, the control

will exit the Louver Configuration
mode.

Figure 6