sEqUEnCE of opErAtion – WALL moUntEd tHErmostAt modE

place the system switch in Heat mode.

Adjust the set-point temperature above

the room temperature. The compres-

sor and fan motors will start and heating

will begin. Depending on the thermostat

selected, electric heat will also energize
when the deviation between room tem-

perature and set point temperature is high

enough to call for second stage heating.

(See the thermostat owner’s manual for

this feature) Place the set-point tempera-

ture below the room temperature. The
outdoor condenser and electric heat will

stop while the indoor fan will remain on for

an additional sixty seconds.

other features

Short Cycle Protection (ASCT):

The electronic control incorporates an

anti-short cycle timer (ASCT) feature de-

signed to protect the compressor from

short cycling. The ASCT is activated im-

mediately following the off cycle of the

outdoor unit. Once the room temperature

is satisfied and the outdoor unit switches

off, the ASCT will not allow the outdoor to

restart unit a three-minute time period has

elapsed.

This feature will prevent the compres-

sor and heat source from rapid re-starts.

Once switched off, including following a

power outage, the compressor or heat

source shall not re-start for a minimum of
three minutes.

Staggered Start Protection:

Designed for systems with electric heat,

in heat pump and dry modes the stag-

gered start feature will prevent the com-

pressor and electric heater from starting

simultaneously. There is a thirty-second

delay between the start of the compres-

sor and start of the electric heater while in

Dry mode and Heat pump mode.

Minimum Run Time:

Once started, the minimum on time pre-

vents either the compressor or heat

source from cycling off prematurely. The

minimum ON time for both the compressor

and electric heat is two minutes. Minimum

on time is available only while the control

is configured for Unit mounted keypad op-

eration. Minimum on times are disables
while in Remote thermostat mode.

LCD Back Light:

The LCD display can be illuminated using

the LCD back light feature. The selectable

settings are “Off”, “On”, and “Intermittent”

and can be set in the Configuration mode.

By selecting “Off” the backlight will remain

off at all times. By selecting “On” the back-

light will remain on at all times including

while in the Off mode interface. If “Inter-

mittent” is selected, the backlight will re-

main for 10 seconds after the push of any
button while the control is in the On mode

or after the push of the “ON/OFF” button

while in the Off mode interface.

Drain Pan Sensor:

The drain pan sensors monitor the con-

densate level in each of the units drain

pans. Should the water in either pan
reach a critical level, the monitor will auto-

matically signal the main control unit. The

controls microprocessor will in turn switch

off the condensing unit for a minimum of

three minutes and until the fault condi-

tion has been cleared, to prevent further

condensate production. A fault code “E02”

will then flash on the controls LCD display

and will automatically reset once the fault
condition is cleared.

Annunciation:

The unit is equipped with an annunciation

feature where by the control will beep pro-

viding the user with audio feedback confirm-

ing that the microprocessor has received its

commands. The annunciation feature must

be activated in the Configuration mode. The

selections are “Off” and “On”. If “Off” is se-

lected, annunciation will remain off. If “On”

is selected then annunciation will beep with

the push of any button in the On mode or

with the push of the “ON/OFF” button while

in the Off mode interface.