WLCA/WLHA High Wall Evaporator

18

or Down arrow buttons will allow selection

of six different fixed louver positions or
auto (oscillation) mode. The sequence is

01, 02, 03, 04, 05, 06 and Auto. Once the

desired setting is selected, press the Fan/

Louver button momentarily or let idle for
10 seconds to exit the louver set mode.

While the control is in the On mode,

the louver will remain in the selected

louver position. If Auto louver operation

is selected, the louver will oscillate only

when the fan is running. When the control

is turned off via the ON/OFF button the

louver will return to the closed position.

Cool mode

For cooling operation first turn the unit

on via the ON/OFF button. Select Cool

mode via the MODE button. The room

temperature and set point temperature

will be displayed. The setpoint tempera-

ture can be changed with each succes-

sive press of the Up or Down arrow but-

tons or by holding the button in.

Place the setpoint temperature below

the room temperature. The compressor

will start and cooling will continue for a

minimum of two minutes and as long as

the setpoint remains below room temper-

ature. Once the room temperature is sat-

isfied for at least 60 seconds and the two-

minute minimum run time has elapsed

the compressor will cycle off. The fan will

operate as described in “Fan Operation”.

notE:

Once the compressor is

switched off, or after a power outage

there is a three-minute delay before

the compressor will re-start.

Heat mode

Optional Electric Heat Operation

(Non Heat pump condenser units only):

For operation with electric heat the

control must first be configured properly

(Heat source – “ON”, Heat pump – “OFF”).

See: Configuration Interface mode.
For electric heat operation, first turn the

unit on via the ON/OFF button. Then se-

lect Heat mode via the MODE button. The

room temperature and setpoint tempera-

ture will be displayed. Press either the

Up or Down arrow buttons to change the

setpoint temperature. The setpoint tem-

perature will change by one degree with

each successive press of the Up or Down

arrow buttons. Holding the button in will

change the temperature rapidly.

Place the setpoint temperature above

room temperature. The electric heat will

energize and heating will continue as

long as the setpoint remains above room

temperature. When the room temperature

has been satisfied for at least 60 seconds
and the two minute minimum on time has

expired, the electric heat will switch off.

The fan will operate as described in “Fan

Operation”.

Optional Heat Pump With Electric

Heat

(2-stage heating):

For heat pump operation with electric

heat the control must first be configured

properly (Heat source – “ON”, Heat pump –

“ON”). See: Configuration Interface mode.

For heat pump operation with backup

electric heat, first turn the unit on via the

ON/OFF button. Then select Heat mode

via the Mode button.

The room temperature and setpoint

temperature will be displayed. Press either

the Up or Down arrow buttons to change

the setpoint temperature. The setpoint

temperature will change by one degree

with each successive press of the Up or

Down arrow buttons. Holding the button in

will change the temperature rapidly.

Place the setpoint temperature above

the room temperature by one degree. The

compressor will start and heating will con-

tinue for a minimum of two minutes and as

long as the setpoint remains above room

temperature. When the room temperature

has been satisfied for at least 60 seconds

and the minimum on time has elapsed,

the compressor will switch off. The fan will

operate as described in “Fan Operation”.

Next, place the setpoint temperature

above the room temperature by at least

two degrees. The compressor will start

and, the electric will also energize after a

30 second delay, thus two-stage heating.

The electric heat will run for a minimum

of two minutes and until the deviation

sEqUEnCE of opErAtion – Unit moUntEd KEy pAd modE