WLCA/WLHA High Wall Evaporator

the desired fan setting in all modes except

Dry mode. In Dry mode, the fan will oper-

ate constantly at low speed. The LCD will

indicate fan speed selection.

High and Low are constant fan settings.

The fan will operate continuous regardless

of set point or room temperatures. Auto

mode is for cycling fan operation.

Auto Fan mode can only be selected if

the unit is in Heat, Cool or Auto Change-

over modes. In Auto Fan mode the fan

will cycle with the call for Heat or Cool.

Fan speed will be determined by the mi-

croprocessor and speed adjustment will

be made according to room and setpoint

temperatures. The fan will switch to High

speed when room temperature deviates by

more than two degrees from setpoint. The

fan will switch to Low speed if the devia-

tion is one degree or less. When the room

temperature reaches setpoint temperature

the heat/cool call will then be dropped. The

fan will stay on for an additional 60 sec. to

purge unit of any residual energy.

If the Room Air Sampling feature has

been enabled in the Configuration mode

(see Configuration mode), after the fan

has been off for the selected time, it will

then cycle on for 60 seconds. The unit will

circulate room air to remove any temper-

ature stratification by the unit so the mi-

croprocessor can determine an accurate

room temperature. After the 60 second

room air sample time has elapsed, and

if the setpoint temperature remains satis-

fied, the fan will cycle off.

When the unit is in Dry mode the fan

speed will remain constant at Low speed.

While the unit is in Fan mode, Auto is by-

passed and only High or Low are available.

Louver operation

When the control is in the Off mode

the louver will remain in the closed posi-
tion. When the unit is turned on via the ON/

OFF button the louver will open and oper-

ate according to the setting selected in the

Louver Configuration mode.

To enter the Louver Configuration

mode, press and hold the Fan/Louver

button in for three seconds. This will enter

the Louver Configuration mode and “Lou”

will display on the LCD. Pressing the Up

sEqUEnCE of opErAtion – Unit moUntEd KEy pAd modE

on/off

Pressing the “on/off” button once

will switch the unit either on or off. In the

Off mode, the LCD will display the time of

day and day of the week. In the On mode

the LCD display will also display the room

temperature and the mode of operation

Cool, Heat, Auto (Auto changeover), Dry

or Fan mode. While in the On mode, the

set point temperature will display momen-

tarily with the push of any button except

the ON/OFF button.

mode of operation

The “modE” button allows the se-

lection of the mode of operation, Cool,

Heat, Auto changeover (ACO). Dry or

Fan mode. In Fan mode either “HIGH” or

“LOW” will be displayed on the LCD.

fan operation

The indoor unit utilizes a two-speed

motor with three operational fan modes.

The FAN button will allow the selection of

For unit mounted key pad operation

the control must be configured through

the Configuration mode. Be sure to select

Remote – OFF in the configuration menu.

(See Configuration mode)

Note:

When power is first applied to the

control or after a power outage there is

a three minute delay before the com-

pressor or electric heat will energize.

This is to protect the unit from short cy-

cling due to loss of power.

Unit mount infrared

Control operation

EMI Air Handlers are equipped with a unit

mount, infrared compatible control pack-

age. This user friendly, microprocessor

control is designed to optimize system

performance and protect the refrigeration

system from unwanted short cycling and

evaporator freeze-ups. Operation of the

unit can be made by either the keypad
on the unit or by using the optional
hand held infrared controller.