29

WLCA/WLHA High Wall Evaporator

troUBLEsHootinG

Emi Air Handlers With

Unit mount infrared Controls

All service should be performed by a

qualified service technician. Before

removing access panels or control

covers to expose moving parts of

non-insulated live electrical compo-

nents for service, disconnect all high

Volt power supplies to both the indoor

unit and outdoor unit. Failure to do so

could result in physical injury and/or

electrical shock.

When trouble-shooting the indoor unit,

please refer to the wiring diagram that is

supplied with the equipment. It is located on

the inside surface of the left end cap. (Also

refer to Locate Electrical Wiring section

in the front of this instruction.) If you are

unable to locate the wiring diagram please

feel free to call the factory technical service

line at (800) 228-9364 and one can be faxed

or mailed. Please have the full model and

serial number available prior to calling.

EMI America Series evaporators are

designed to operate with EMI America
Series

condensers. The evaporator (indoor

unit) and condenser (outdoor unit) are to be

independently connected to the electrical

service panel and protected by separate

time delay fuse or HACR breakers. (See the

unit name plate for the correct breaker type
and size). The indoor and outdoor units are

also connected to each other via a 24V inter-

connect wiring. A transformer provides the
low

Volt power source for the controls. The

number of low Volt interconnect conductors

will be two to six depending on heating op-
tions and or thermostat selection. Intercon-

nect wire should be at least 18 awg. Refer to

the unit wiring diagram for the interconnect

diagram that matches your system.

mAintEnAnCE And troUBLEsHootinG proCEdUrE

mAintEnAnCE

5. The unit may be wiped with a damp cloth

when needed.

note:

Do not run the unit without the

filter or the grille.

Figure 1A

Not used

4. Vacuum dust from the return air grille and

coil surface when cleaning the filter.

!

!

WArninG

Advertising