4. Troubleshooting (DeviceNet)

Countermeasure 2: Disconnect the shield wire to isolate it from the ground.

When noise intrudes the ground line because a noise source such as an inverter is
installed near the communications power supply, disconnect the shield wire of the
communication cable and isolate it from the ground to restrain noise intrusion.

Power Supply Tap

V+

CAN H

Shield (S)

CAN L

V-

V+

CAN H

Shield (S)

CAN L

V-

V+ V- S

V+ V- FG

Communications

Power Supply

24 V DC

Ground 100

Ω or less.

DeviceNet cable

Disconnect here.

♦ Induced noise via communication cable

Separate the DeviceNet signal wire from the other wires (especially power wires).

* Separate the signal wire from the power wires 300 mm or more.

Light electrical cable
Communication cable

Control cable

Power cable

Signal wire

PLC input/output wire

PLC power wire

Control circuit wire

Power wire

Suspended ducts

Floor ducts

1

2

1

2

1 2

1 Signal wire

PLC input/output wire

2 Power wire

300 mm

or more

Conduit

300 mm

or more

During site inspection, bypass the wire that is possibly affected by induced noise with other
cables and then lay the cables. Establish the communication under no induced noise
condition and verify whether an error occurs.