2. Installation

Total Drop Line Length

The total drop line length is the total distance of all drop lines on one network.

Trunk Line

2 m

2 m

1 m

1 m

3 m

4 m

4 m

Terminating

Resistor

Terminating

Resistor

In the figure above, the total drop line length is 17 m.

The maximum total drop line length is restricted by baud rate as shown in the table below.
The cable thickness is not related to the restriction.

Baud Rate

Max. Total Drop Line Length

500 kbps
250 kbps
125 kbps

39 m
78 m

156 m

Cable Current Capacity

The current-carrying capacity of the DeviceNet network cable is restricted as shown below:

Trunk Line

Thick Cable

Thin Cable

Drop Line (Unit: A)

Current Capacity

8A

3A

4.57 / Drop Line Length (m) ≤ 3A

The following figures illustrate power supply configuration examples.

When an external power supply is installed on the network as shown in the figure below, the
current capacity is 11A and it exceeds the permissible current of the cable.

Trunk Line

1A

Power Supply Tap

External Power

Supply 24 V DC

1A

1A

2A

2A

2A

2A

Terminating

Resistor

Terminating

Resistor

If the location of the external power supply is changed on the network as shown in the figure
below, the power supply can be used on the network because the current capacity on the left
side of the power supply tap is 5 A and that on the right side is 6 A.

Trunk Line

1A

Power Supply Tap

1A

1A

2A

2A

2A

Terminating

Resistor

External

Power Supply

24 V DC

2A

Terminating

Resistor

Fieldbus I/O Rev.6