Epson EM07ZS1647F User Manual

Page 97

Advertising
background image

4. Troubleshooting (DeviceNet)

♦ Causes of Error

Possible Cause

Examination Method

Countermeasure

{ Disconnected

terminating resistors

{ Cable disconnection
{ Disconnected

connector

{ Disconnected signal

wire

(1) Check that terminating

resistors are connected to
both ends of the network.

(2) Measure resistance

between signal wires with
communications power
supply OFF.
→ Normal: 50 to 70

z Measuring point: Connection

of the trouble unit

z For detail, refer to the section

4.1.3.1 Connection Problem.

Fix the problem.

How to find the trouble
point:
Remove the terminating
resistor on one end of the
network. The trouble point
is where resistance changes
from 120

Ω.

{ Loose connector
{ Loose signal wire

Check for the connection of
connectors and signal wires.
→ The connectors and signal
wires should be firmly
connected.
z Checkpoint: all nodes and all

branch taps

z For details, refer to the

section 4.1.3.2 Loose
Connector and Signal Wire
.

Connect the connectors and
signal wires again.

{ Voltage drop of

communications
power supply

Measure voltage of
communications power supply
at the unit with a trouble.
→ Normal: 11V or more
between V+ and V-
z If the voltage is 11 to 14 V,

the unit is a possible cause.
Fix the problem on the unit.

Check the voltage of the
power supply.
Calculate the current
capacity of the cable and add
more communications power
supplies.

{ Noise

(external cause)

Check the noise intrusion via
the following paths (1) to (3).
(1) Noise via DRAIN (FG)
(2) Induced noise via

communication cable

(3) Communications power

supply

→ For details, refer to the

section 4.1.3.3 Noise
Intrusion
.

Take countermeasures
against noise.

{ Broken unit

Replace the broken unit with a
new one.
→ Verify whether the problem

is fixed.

Replace the unit with a new
one.

z No cause is

identified.

Identify the trouble point by
dividing the network.
→ For details, refer to the

section 4.1.3.4 Broken Unit
Examination
.

Fieldbus I/O Rev.6