4. Troubleshooting (DeviceNet)


Status Code

General

Protocol

Descriptions

45

Non-resident

dialogue

software.

Additional information:
Initialize the applicomIO® interface before use by
running the PcInitIO

47

Targeted

applicomIO®

card invalid or incorrectly

initialized by the function IO_Init

53

Synchronization problem on the line.
Additional information:
The DeviceNet master is "off line" (power supply
not detected or the CAN component of the
applicomIO® is "Bus Off")
Check the network wiring and Baud Rate.

55

Response time-out exceeded.
Additional information:
The device accepted the connection but did not
answer the request.
Check the device status.

65

Connection

denied.

Additional information:
Connection to the DeviceNet master is in progress
or refused by the device.

70

Connection finished.
Additional information:
Duplication of MAC ID detected on the DeviceNet
network.
Modify the MAC ID of the DeviceNet master.

79

Profile incompatible.
Additional information:
The device does not match the configuration.
Check the device identity and the connection sizes.

63

Indicates that a communication error has been
encountered on serial Port.

66

Not enough applicomIO® interface memory.

93

Driver cannot be accessed.

99

Indicates that applicomIO® solution is already
running.

255

Indicates that the local input buffer was not updated
beforehand by the function IO_RefreshInput.

Fieldbus I/O Rev.6

109