4. Troubleshooting (PROFIBUS DP)

♦ Causes of Error

Possible Cause

Examination Method

Countermeasure

{ Electrical surges of

device power supply

Measure voltage of device
power supply at the trouble
unit.
→ It should be within the range

of sufficient voltage for
device operation.

Check voltage of the device
power supply.

{ Disconnected

terminating resistors

{ Cable disconnection
{ Disconnected

connector

{ Disconnected signal

wire

(1) Check that terminating

resistors are connected to
both ends of the network.

(2) Measure resistance

between signal wires with
device power supply OFF.

→ Normal: 100 to 120

z Measuring point: Connection

of the trouble unit

z For detail, refer to the section

4.2.3.1 Connection Problem.

Fix the problem.

How to find the trouble
point:
Remove the terminating
resistor on one end of the
network. The trouble point
is where resistance changes
from 220

Ω.

{ Loose connector
{ Loose signal wire

Check for the connection of
connectors and signal wires.
→ The connectors and signal

wires should be firmly
connected.

z Checkpoint: all stations and

all branch taps

z For details, refer to the

section 4.2.3.2 Loose
Connector and Signal Wire
.

Connect the connectors and
signal wires again.

{ Broken unit

Replace the trouble unit with a
new one.
→ Verify whether the problem

is fixed.

Replace the unit with a new
one.

122

Fieldbus I/O Rev.6