Step 2 framing the fireplace – Heat & Glo Fireplace 6000 XLT User Manual

Page 10

Advertising
background image

7

Minimum Clearances from the Vent Pipe to

Combustible Materials

For Vertical

For Horizontal Sections

Sections

At Wall Firestops

Top

Bottom

Sides

Top

Bottom

Sides

3 inches

1 inch

1 inch

1 inch

2-1/2 inches 1/2 inch

1 inch

(75 mm) (25 mm) (25 mm)

(25 mm)

(63.7 mm)

(13 mm) (25 mm)

For minimum clearances, see the direct vent
termination clearance diagrams on pages 25 and 27 in
this section.

Step 2
Framing the
Fireplace

Fireplace framing can be built before or after the
fireplace is set in place. Framing should be positioned
to accommodate wall coverings and fireplace facing
material. The diagram below shows framing reference
dimensions.

CAUTION

MEASURE FIREPLACE DIMENSIONS, AND
VERIFY FRAMING METHODS AND WALL
COVERING DETAILS, BEFORE FRAMING
CONSTRUCTION BEGINS.

A

B

C

Framing should be
constructed of 2 X 4
lumber or heavier.

Model

A

B

C

D

8000DVTFL

49

42-3/8

25-3/8 47

6000DVTFL & 6000XLT 42

38-1/4

22 43-1/4

6000ARCH

42*

42-3/8

22 53-5/8

48-1/4**

SL-42DVT

49

42-7/8

17 45-3/4

Figure 5. Framing Dimensions

NOTE: DIMENSIONS SHOWN IN INCHES

*SURROUND IN FRONT OF FINISHED WALL

**SURROUND FLUSH WITH FINISHED WALL

The framing
headers may
rest on the
fireplace
stand-offs.