Heat & Glo Fireplace 6000 XLT User Manual

Page 30

Advertising
background image

27

Roof Pitch

H (min.) ft.

flat to 6/12

1.0

6/12 to 7/12

1.25

over 7/12 to 8/12

1.5

over 8/12 to 9/12

2.0

over 9/12 to 10/12

2.5

over 10/12 to 11/12

3.25

over 11/12 to 12/12

4.0

over 12/12 to 14/12

5.0

over 14/12 to 16/12

6.0

over 16/12 to 18/12

7.0

over 18/12 to 20/12

7.5

over 20/12 to 21/12

8.0

Figure 26. Minimum Height from Roof to Lowest

Discharge Opening

To seal the roof hole, and to divert rain and snow from
the vent system:

• Attach a flashing to the roof using nails, and use a

non-hardening mastic around the edges of the
flashing base where it meets the roof.

• Attach a storm collar over the flashing joint to form a

water-tight seal. Place non-hardening mastic
around the joint, between the storm collar and the
vertical pipe.

• Slide the termination cap over the end of the vent

pipe and rotate the pipe clockwise 1/4 turn.

1. Attach the flashing

and apply sealant
around the edges of
the flashing base.

2. Attach the storm

collar over the flashing
joint and apply sealant
between the storm
collar and vertical
pipe.

TERMINATION
CAP