For Vertical Runs - The vent system must be
supported every eight (8) feet (2.4 m) above the
fireplace flue outlet by wall brackets.

To install support brackets for vertical runs:

• Attach wall brackets to the vent pipe and secure

the wall bracket to the framing members with nails
or screws.

Use wall brackets to
support vertical runs
every 8 feet (2.4 m)
above the fireplace flue
outlet.

Figure 18. Installing Support Brackets

4. Install Firestops

For Horizontal Runs - Firestops are REQUIRED
on both sides of a combustible wall through which
the vent passes.

NOTE

Model DVK-01TRD and SLK-01TRD do not need
an exterior firestop on an exterior combustible wall.

To install firestops for horizontal runs that pass
through either interior or exterior walls:

• Cut a 12-inch by 12-inch (305 mm X 305 mm)

hole through the wall for D-series or a 10-inch by
10-inch (254mm X 254mm) hole for SL-D-series
pipe. The center of the hole is one (1) inch (25.4
mm) above the center of the horizontal vent pipe.

8 FT (2.8 m)

WALL
BRACKET

WALL
BRACKET

WALL
STUD

WALL
STUD

FLUE
OUTLET

FLUE
OUTLET

1" MIN.
25.4 mm)

1" MIN.
25.4 mm)