Section 3: installing the fireplace – Heat & Glo Fireplace 6000 XLT User Manual

Page 9

Advertising
background image

6

3

Installing the
Fireplace

Step 1
Locating the
Fireplace

The diagram below shows space and clearance
requirements for locating a fireplace within a room.

Figure 4. Fireplace Dimensions, Locations, and

Space Requirements

Clearance Requirements

The top, back, and sides of the fireplace are defined
by stand-offs.

Minimum Clearances from the Fireplace to

Combustible Materials

Glass

Back of

Sides of

Top of

Front

Floor

Fireplace

Fireplace

Fireplace

Ceiling

36 inches

0

1/2 inch

1/2 inch

3-1/2 inches

31 inches

(914 mm)

(13 mm)

(13 mm)

(89 mm)

(787 mm)

The minimum clearance to a perpendicular wall
extending past the face of the fireplace is one inch (25
mm).

For 6000 Series Models, the back of the fireplace may
be recessed 21-1/2 inches (546 mm) into
combustible construction.

For the 8000 DVTFL, the back of the fireplace may be
recessed 24-7/8 inches (641 mm) into combustible
construction.

For the SL-42DVT, the back of the fireplace may be
recessed 16 1/2-inches (419mm) into combustible
construction.