D. how to use the vent graph, E. venting guidelines – Heat & Glo Fireplace Heat & Glo PALOMA-BZ-MOD User Manual

Page 12

Advertising
background image

Heat & Glo • PALOMA-BZ-MOD, PALOMA-GR-MOD, PALOMA-GY-MOD • 2189-900 Rev. i • 5/12

12

EX. 2

EX. 1

2' 4' 6' 8' 10' 12' 14' 15'

30'

28'

26'

24'

22'

20'

18'

16'

14'

12'

10'

8'

6'

4'

2'

0'

(MAX)

(MIN)

32'

34'

35'

11-5/8”

2 ft. (610 mm) Maximum Horizontal run with no
vertical pipe and with 1/4 in. (6 mm) rise per foot.

6 ft. (2 m) Minimum

Vertical Termination

For rear vent or top
of appliance for top
vent.

C

L

6 in. (152 mm) Minimum starter pipe

C

L

VERTICAL DISTANCE

FROM APPLIANCE

TO THE 90º ELBOW

TOTAL HORIZONTAL RUN TO

OUTSIDE OF EXTERIOR WALL

(INCLUDING ELBOWS)

To adjust the vent restrictor

plate, see page 34.

VENT RESTRICTOR

PLATE REQUIRED

Figure 5.2

D. How to Use the Vent Graph

1. Measure the distance from the top of appliance to the

center of the 90° elbow. On the graph below, draw a
horizontal line from that measurement on the vertical
axis across until it intersects with the slanted line.

2. From the point of this intersection, draw a vertical line

to the bottom of the graph.

3. The point at which this line meets the bottom line of the

graph is the maximum length of the horizontal run.

Example 1: If the vertical dimension from the top of the
appliance to the center of the 90° elbow is 7 ft. (2 m), the
horizontal run to the outer wall fl ange must not exceed 13
ft. (4 m).

Example 2: If the vertical dimension from the top of the
appliance is 21 ft. (6.4 m), the horizontal run to the outer
wall fl ange must not exceed 9 ft. (3 m).

4. Each 90° elbow is equivalent to 3 ft. (914 mm) of vent

pipe and each 45° elbow is equivalent to 1 ft. (305
mm) of vent pipe, and must be subtracted from vent
pipe run. A single vertical to horizontal 90° elbow is
already calculated into the allowable 15 ft. (5 m) run.
Each additional 90° elbow reduces the maximum
horizontal distance by 3 ft. (914 mm).

Example: The use of three elbows would reduce the
allowable horizontal run to 9 ft. (3 - 1 = 2 elbows x 3 ft.
= 6 ft.; 15 ft. max. - 6 ft. = 9 ft. max.)

E. Venting Guidelines

• The maximum horizontal vent run is 15 ft. (5 m) when

the vertical vent rise is 10 ft. (3 m).

• The minimum horizontal vent run is 11-5/8 in. (295 mm).

• Horizontal sections require a 1/4 in. (6 mm) rise for

every 12 in. (305 mm) of horizontal travel.

• Horizontal sections require noncombustible support

every 3 ft. (914 mm), e.g. wall strap.

• Wall thickness: Minimum 4 in. (102 mm). Maximum 20

in. (508 mm).

• Vent Diameter: Exterior 6-5/8 in. (168 mm); Inner 4 in.

(102 mm).

EXCEPTION FOR REAR VENT KIT, HORIZONTAL
INSTALLATION:

• The maximum horizontal vent run is 2 ft. (610 mm).

NOTICE: Maximum horizontal vent run is 18 in. (457
mm) when using the HRC termination cap.

• The maximum horizontal vent run with a 45° elbow is 18

in. (457 mm).

• No external minimum rise is required. The minimum

horizontal vent run is 11-5/8 in. (295 mm).

• For any vertical rise when rear venting, a minimum of 2

ft. (610 mm) vertical must be used prior to any horizontal
run.

Advertising