Heat & Glo Fireplace Heat & Glo PALOMA-BZ-MOD User Manual

Page 41

Advertising
background image

41

Heat & Glo • PALOMA-BZ-MOD, PALOMA-GR-MOD, PALOMA-GY-MOD • 2189-900 Rev. i • 5/12

RED JUMPER
WIRE TO
BROWN

WH

IT

E

ORANGE

INTERMITTENT
PILOT IGNITOR

IGNITION MODULE

3 VAC

REMOTE RECEIVER

ORANGE

GREEN

BLACK

RED

VALVE

GROUND TO
FIREPLACE CHASSIS

TRANSFORMER

3 VAC

PLUG

IN

ORANGE

ORANGE

RED

RED

FLAME
CONTROL
SOLENOID

BATTERY PACK

I

S

RED

RED

ORANGE

ORANGE

BRN

ORANGE

ORANGE

BRN

PIGGYBACK

ON/OFF SWITCH

RED

RED

BRN

REMOTE

RECEIVER

Figure 8.31 Remote Control IPI Wiring Diagram

Wiring the flame control solenoid:

Connect the two leads from the flame control solenoid to
the orange leads from the receiver. See Figure 8.31.

Install a manometer into the pressure tap. Plug the remote
receiver into the 110-120 VAC power supply.

Light the appliance as directed in Section 9 of this manual.
Set the manifold pressure on the gas valve by rotating the
flame control solenoid. Adjust until the reading on the
manometer is 3.5 in. W.C. for natural gas or 10 in. W.C.
for LP.

Tighten the jam nut to the face of the variable regulator
body. See Figure 8.30. Turn the main gas knob on the gas
valve OFF. Remove the manometer from the pressure tap
and screw the tap closed.

Follow the instructions from the remote control kit to
operate and program the remote control.