T775A/B/M SERIES 2000 CONTROLLER

CHECKOUT

62-0254–03

10

CHECKOUT

Inspect all wiring connections at the controller terminals,
and verify compliance with the installation wiring
diagrams.

WARNING

Electrical Shock Hazard.
Can cause severe injury, death or property
damage.
Disconnect power supply before beginning wiring
or making wiring connections, to prevent electrical
shock or equipment damage.

If any wiring changes are required, first be sure to remove
power from the controller before starting work. Pay
particular attention to verifying the power connection (24,
120, or 240 Vac).

After the controller is installed and wired, apply power.

Power Loss

The date and time settings are retained for 24 hours after
a power outage. After a power loss of more than 24 hours,
the date and time settings may need to be reentered. All
other settings are stored permanently.

Temperature Sensor Calibration

As wire length increases, resistance increases and thus
the temperature reading increases. If necessary, calibrate
the sensor input by reducing the value by the amount
shown in the Table 3. For example, a wire run with 18
gauge wire of 1,000 feet, requires a calibration offset of
-6.0°F.

IMPORTANT

If the calibration value in the table exceeds the
controller’s calibration limits of +/-10°F (+/-6°C),
you must use a heavier gauge wire.

For example, with a wire run of 1,000 feet you
must use 20 AWG wire or heavier in order to cal-
ibrate for wire loss within the limits of the control-
ler.

See “2.2.2.2. CALIBRATE (the sensor)” on page 18 for
the instructions to enter the calibration value.

Fig. 21 shows how sensor resistance varies with
temperature for a sensor having a positive temperature
coefficient (PTC) of 2.1 Ohms per degree F (3.85 Ohms
per degree C).

Fig. 21. Sensor Resistance vs. Temperature.

Table 3. Temperature Sensor Calibration for

Resistance Loss due to Wire Length.

AWG

Rating

m

/ft

Temperature Offset in

°F (Foot)

a

a

This is the distance from the controller to the sensor
(already accounts for round trip distance).

200 ft

500 ft

1,000 ft

14

2.5

0.46

1.14

2.28

16

4.0

0.72

1.82

3.64

18

6.4

1.16

2.90

5.82

20

10.2

1.86

4.64

9.28

22

16.1

2.92

7.32

14.64

AWG

Rating

m

/m

Temperature Offset in

°C (Meter)

a

100 m

200 m

300 m

14

8.3

0.44

0.86

1.30

16

13.2

0.68

1.38

2.06

18

21.0

1.10

2.18

3.28

20

33.5

1.74

3.48

5.22

22

52.8

2.74

5.48

8.22

M24304

TEMPERATURE (DEGREES)

RESISTANCE (OHMS)

1403

1317

1231

1145

1059

973

20

40

60

80 100 120 140 160 180 200 220

0

10 20 30 40 50 60 70 80 90 100

°F

°C

0

-20

-40

120

110

250

-40

-20 -10

-30

1489

887

801

1097 ± 0.08 OHMS

AT 77°F (25°C)

POSITIVE TEMPERATURE COEFFICIENT (PTC) OF 2.1 OHMS PER °F