1. PROGRAMMING

62-0254–03

14

Programming the T775A/B/M Controller

To program the controller, perform the following
procedures in the order listed:

1.

Enter Program mode — see “1.1. Entering Program
Mode”

2.

Program the Outputs — see “1.2. Program Menu for
Outputs” on page 14

When programming is complete, you may continue with
“3. Scheduling” on page 30 or, for advanced options,
continue with “2. Setup (Advanced Options)” on page 17.

Fig. 26. Program Menu.

1.1. Entering Program Mode

Press the MENU button, then select PROGRAM and
press the

X button to view the Program menu.

Fig. 26 shows the Program menus for controllers with and
without Modulating Outputs.

NOTE:

Modulating outputs are not available on the
T775A and T775B controller models.

Fig. 27. Program Menu Outputs.

1.2. Program Menu for Outputs

Press the MENU button, select PROGRAM, then select
RELAY 1 (or MOD 1) to view the parameters. Fig. 27
shows RELAY 1.

NOTE:

For MOD 1 and 2, THROT RNG replaces
DIFFRNTL.

NOTE:

The Setback parameter displays only if schedul-
ing is enabled (see Fig. 55 on page 24) or the DI
Option is set to Setback. (see Fig. 57 on
page 25).

Continue with “1.2.1. SETPOINT”.

Fig. 28. Program - Setpoint.

1.2.1. SETPOINT

1.

From the menu, use the

S and T buttons to high-

light SETPOINT.

2.

Press the

X button to display the setpoint value.

3.

Use the

S and T buttons to increase/decrease the

desired setpoint temperature.

Default: 70°F (21°C)
Range: -40°F to 248°F (-40°C to 120°C)

4.

Press the

X button to accept the setpoint tempera-

ture and display the next option.

OR

MENU

PROGRAM

MENU

PROGRAM

M24492

RELAY 1

RELAY 2

RELAY 3

RELAY 4

EXIT

MENU

PROGRAM

MOD 1

MOD 2

RELAY 1

RELAY 2

RELAY 3

RELAY 4

EXIT

PROGRAM

RELAY 1

MENU

PROGRAM

RELAY 1

SETPOINT

DIFFRNTL

SENSOR

HEAT/COOL

SETBACK

EXIT

M24493

ENTER

SETPOINT

FOR

RELAY 1

PROGRAM

RELAY 1

SETPOINT

MENU

PROGRAM

RELAY 1

SETPOINT

70

F

o

M24494

Advertising