Derivative, Schedule, Exit – Van Air Systems FP-4 Kit User Manual

Page 31

Advertising
background image

2. SETUP (ADVANCED OPTIONS)

T775A/B/M SERIES 2000 CONTROLLER

23

62-0254–03

Fig. 50. Setup - Outputs - Mod Out - Derivative.

2.3.1.4. DERIVATIVE

The Derivative default value is factory set to zero (no
derivative control). It is strongly recommended that the
derivative remain at zero (0) unless you have a very good
reason to adjust it. Derivative control is not needed in the
vast majority of HVAC applications.

1.

From the Mod menu, use the

S and T buttons to

highlight DERIVATIV.

2.

Press the

X button to display the Derivative sec-

onds.

3.

Use the

S and T buttons to increase/decrease the

value.

Default: 0 (zero)
Range: 0 to 3,600 seconds

4.

Press the

X button to accept the seconds and

return to the Mod menu.

Fig. 51. Setup - Outputs - Mod Out - Schedule.

2.3.1.5. SCHEDULE

The Schedule option displays only if the USE SCHED
parameter is set to Yes (see page 24).

1.

From the Mod menu, use the

S and T buttons to

highlight SCHEDULE.

2.

Use the

S and T buttons to highlight YES or NO.

Default: YES

3.

Press the

X button to accept the selection and

return to the Mod menu.

Each output can be set up to follow or ignore the built in
scheduler. To disable the scheduler for all outputs, see
“2.3.3.1. USE SCHED” on page 24.

Fig. 52. Setup - Outputs - Mod Out - Exit.

2.3.1.6. EXIT

Press the

W button (or highlight EXIT and press the X

button) to exit the Mod menu and return to the Outputs
menu.

If you have a second modulating output to configure, go to
“2.3.1. Setting up the Modulating Outputs” on page 21.

If you are finished setting up the modulating outputs,
continue with “2.3.2. NBR OF RELAYS”.

SETUP

OUTPUTS

MOD 1

DERIVATIV

ENTER

DERIVATIVE

TIME FOR

MOD 1

SETUP

OUTPUTS

MOD 1

DERIVATIV

0

SEC

M24516

SETUP

OUTPUTS
MOD

1

SCHEDULE

SETUP

OUTPUTS

MOD 1

SCHEDULE

USE

SCHEDULE

FOR

OUTPUTS

YES

NO

M24517

SETUP

OUTPUTS

MOD 1

TYPE

MIN OUT %

INTEGRAL

DERIVATIV

SCHEDULE

EXIT

M24518