Min off, Di options, Show rt – Van Air Systems FP-4 Kit User Manual

Page 33

Advertising
background image

2. SETUP (ADVANCED OPTIONS)

T775A/B/M SERIES 2000 CONTROLLER

25

62-0254–03

Fig. 56. Setup - Outputs - Options - Min Off Time.

2.3.3.2. MIN OFF

(minimum off time for all relays)

This is the minimum number of seconds of “off time” for
all relays.

1.

Press the

X button to display the Min Off value.

2.

Use the

S and T buttons to increase/decrease the

desired number of seconds from 0 to 990 seconds
in 10 second increments.

Default: 0 (zero)
Range: 0 to 990 seconds

3.

Press the

X button to accept the seconds and

display the DI OPTIONS.

NOTES:

1.

The minimum off time applies to all relay
outputs.

2.

When minimum off time is active, relays
waiting to be energized display a flashing
square underneath the relay number on the
home screen.

3.

If the minimum off time is not equal to zero
(0), the minimum off time activates at power-
up. To manually override, press the

W button

at any time.

Fig. 57. Setup - Outputs - Options - DI Options.

2.3.3.3. DI OPTIONS

(digital input options)

The DI Option you select applies to all outputs. This
option overrides any Setpoint/Setback values entered in
the Schedule.

1.

Press the

X button to display the DI Option selec-

tions.

2.

Use the

S and T buttons to highlight DISABLE,

SETBACK, or IGNORE.

Default: DISABLE

3.

Press the

X button to accept the value and display

the SHOW RT option.

When the digital input (DI) closes, all outputs follow the DI
option value (Disable, Setback, or Ignore):

DISABLE disables the outputs; relays return to de-
energized state and Mod outputs return to 0% output.

SETBACK enables a setback temperature value to be
programmed for each output.

To program the Setback temperature, see Fig. 32
on page 16.

IGNORE causes the digital input to have no effect on
the Relay or Mod outputs.

Fig. 58. Setup - Outputs - Options - Show Runtime.

2.3.3.4. SHOW RT

(show run time hours)

1.

Press the

X button to display the Show RT values.

2.

Use the

S and T buttons to select YES or NO.

Default: YES

3.

Press the

X button to accept the value and return to

the Options menu.

Selecting YES shows the RT (run time) hours for each
relay on the home screen displays.

NOTE:

Run times can be reset to zero for each individ-
ual relay. You must do this for each relay that
you want to reset to zero. See “2.3.4.3. RESET
RT (run time hours)” on page 28.

SETUP

OUTPUTS

OPTIONS

MIN

OFF

ENTER

MINIMUM

OFF TIME

FOR RELAYS

SETUP

OUTPUTS

OPTIONS

MIN OFF

0

SEC

M24522

SETUP

OUTPUTS

OPTIONS

DI OPTS

SETUP

OUTPUTS

OPTIONS

DI OPTS

SELECT DI

OPTIONS

FOR

OUTPUTS

DISABLE

SETBACK

IGNORE

M24523

SETUP

OUTPUTS

OPTIONS

SHOW RT

SETUP

OUTPUTS

OPTIONS

SHOW RT

USE

RUNTIME

FOR

RELAYS

YES

NO

M24524