Throttling range, Setting up the outputs, Setting up the modulating outputs – Van Air Systems FP-4 Kit User Manual

Page 29

Advertising
background image

2. SETUP (ADVANCED OPTIONS)

T775A/B/M SERIES 2000 CONTROLLER

21

62-0254–03

Fig. 44. Setup - Sensors - Sensor B - Throttling

Range.

2.2.4.2. THROTTLING RANGE

(Sensor B only)

The throttling range for the modulating high or low limit
positions the setpoint at the end of the throttling range.
For example, with a high (Heat) limit at Sensor B of 200°F
and a throttling range of 10°F, the modulating output
controlling Sensor A begins to throttle back at 190°F, and
fully closes at 200°F. Conversely, the throttling range for
the low limit begins above the Cooling setpoint in the
same manner.

1.

From the Limit menu, use the

T button to highlight

THROT RNG.

2.

Use the

S and T buttons to increase/decrease the

desired value for the Throttling Range.

Default = 0

3.

Press the

X button to accept the value and return to

the Limit menu.

4.

Press the

W button to exit the Limit menu.

5.

Press the

W button to exit the Sensors menu and

return to the Setup menu.

Fig. 45. Setup - Outputs Menu.

2.3. Setting up the Outputs

1.

From the Setup menu, use the

Sand T buttons to

highlight OUTPUTS.

2.

Press the

X button to display the Outputs menu.

NOTE:

The menus (e.g. the Outputs menu shown here)
can display only those relays that are defined in
Setup (see page 24). For example, if you config-
ure only two relays, then only two relays display
on the appropriate menus.

The following procedures set up each modulating output
and relay output.

Fig. 46. Setup - Outputs - Modulating Output Menu.

2.3.1. Setting up the Modulating Outputs

1.

From the Output menu, use the

S and T buttons to

highlight the desired modulating output (MOD 1 or
MOD 2).

2.

Press the

X button to display the selected MOD

menu.

NOTE:

Modulating outputs are not available on the
T775A and T775B controller models. If you are
setting up one of these controllers, skip to “2.3.2.
NBR OF RELAYS” on page 24.

Use the remaining procedures, beginning with “2.3.1.1.
TYPE (of output signal)”, to set up each modulating
output. If you have two modulating outputs, repeat these
procedures for each modulating output.

SETUP

SENSORS

SENSOR B

UNITS

CALIBRATE

LABEL

LIMIT

HI LIMIT

THROT RNG

EXIT

SETUP

SENSORS

SENSOR B

ENTER

VALUE FOR

SENSOR B

THROTLING

RANGE

SETUP

SENSORS

SENSOR B

THROT RNG

10

F

o

M24510

SETUP

OUTPUTS

SETUP

OUTPUTS

MOD 1

MOD 2

# RELAYS

OPTIONS

RELAY 1

RELAY 2

RELAY 3

RELAY 4

EXIT

M24511

SETUP

OUTPUTS

MOD

1

SETUP

OUTPUTS

MOD 1

TYPE

MIN OUT %

INTEGRAL

DERIVATIV

SCHEDULE

RESET

EXIT

M24512