background image

T775A/B/M SERIES 2000 CONTROLLER

3. SCHEDULING

62-0254–03

32

Fig. 74. Schedule Event Menu (Showing MON-FRI).

3.3. Setting Individual Schedules

As shown in the Schedule menu (Fig. 69 on page 30),
schedules can be set for the following time periods:

Monday through Friday

Saturday and Sunday

Individual days of the week

1.

From the Schedule menu, use the

S and T buttons

to highlight the desired time period.

2.

Press the

X button to display the Schedule menu

for the selected time period.

For each selected time period, the schedule event (E1
and E2) parameters are exactly the same as shown in
Fig. 74.

SCHEDULING EXAMPLE
Setting the schedule is independent of the temperature
settings for the relay outputs. The following illustrates a
weekly schedule for daytime (setpoint) and night time
(setback) use and shows the factory default settings:

To set a schedule, continue with “3.3.1. E1 SETPT
(setpoint for event 1)”.

The following figures show the MON-FRI menu, but the
menu selections are the same for any time period.

Fig. 75. Schedule - Event 1 Setpoint.

3.3.1. E1 SETPT

(setpoint for event 1)

1.

From the selected time period menu, use the

S and

T buttons to highlight E1 SETPT.

2.

Press the

X button to display the setpoint options.

3.

Use the

S and T buttons to highlight the desired

option.

4.

Press the

X button to accept the value and return to

the selected time period menu.

MENU

SCHEDULE

MON-FRI

MENU

SCHEDULE

MON-FRI

E1 SETPT

E1 TIME

E2 SETPT

E2 TIME

EXIT

M24541

Table 4. Mon-Fri Schedule Defaults

DAY

EVENT

SETPT ACTION

TIME

Mon-Fri

Event 1 (E1)

Setpoint

6:00 AM

a

a

Setpoint time span is 6:00 AM until 5:59 PM because
setback starts at 6:00 PM.

Mon-Fri

Event 2 (E2)

Setback

6:00 PM

b

b

Setback time span is 6:00PM until 5:59 AM because
setpoint starts at 6:00 AM.

Sat-Sun

Not used; remains in Setback from Mon-Fri

E2 settings

MAIN

SCHEDULE

MON-FRI

E1 SETPT

MENU

SCHEDULE

MON-FRI

E1 SETPT

SELECT

SETPOINT

FOR

EVENT 1

SETPOINT

SETBACK

NOT USED

M24542

Advertising