Chapter 2 – Explanation of Functions

2.6 Control mode changeover in case of emergency

If the elevator cannot operate in vector mode with feedback mode (due to encoder failure, for
example), the control mode can be changed to V/f or SLV mode to allow short term emergency
operation. Changeover is initiated by an intelligent input configured to the [ECM] function.

NOTE: Do not use this mode as a normal operation mode.

< Additional setting items>

Function

Code

Function Name

Setting

A244

Control mode on

emergency changeover

00: V/f constant torque
01: V/f variable torque
02: sensorless vector SLV
03: 0 Hz domain SLV

C001

- C008

Intelligent input

terminals 1 - 8

Set to 52: ECM

2.7 Braking control function

The following functions are added to the brake control function vs. the standard SJ300 series.
1. Brake ON and OFF frequency

Brake ON frequency and brake OFF frequency can be set separately.

2. Delay time at brake (BRK) OFF

Delay time can be set at brake OFF.


(example 1) Timing chart below shows result when brake confirmation signal (BOK) is not assigned

b121 Waiting time for
releasing brake confirmation

b127 Brake OFF frequency

b125 releasing
frequency

time

b128 Delay time at

brake signal is

turned OFF

RUN command (FW/RV)

Output
frequency

Brake release

Output (BRK)

b123 Waiting time for
release brake confirmation

b122 Waiting time
for acceleration

19