Chapter 3 – Parameter Setting Tables

*P090

Frequency 1 for I-gain
adjustment

0.-max.frequency 0.3

*P091

Frequency 2 for I-gain
adjustment

0. or P090-max.frequency

0.7

*P092

Frequency 3 for I-gain
adjustment

0. or P091-max.frequency

1.0

*P093

Frequency 4 for I-gain
adjustment

0. or P092-max.frequency

2.0

*P094

Frequency 5 for I-gain
adjustment

0. or P093-max.frequency

50.0

*P095

Frequency 6 for I-gain
adjustment

0. or P094-max.frequency

50.0

*P096

Frequency 7 for I-gain
adjustment

0. or P095-max.frequency

50.0

*P097

Frequency 8 for I-gain
adjustment

0. or P096-max.frequency

50.0

P100 I-gain

1

0.-100.(%)

80.

P101 I-gain

2

0.-100.(%)

70.

P102 I-gain

3

0.-100.(%)

60.

P103 I-gain

4

0.-100.(%)

50.

P104 I-gain

5

0.-100.(%)

50.

P105 I-gain

6

0.-100.(%)

50.

P106 I-gain

7

0.-100.(%)

50.

P107 I-gain

8

0.-100.(%)

50.

P110

FW side balance value

0.0-10.0(v)

0.0

P111

RV side balance value

0.0-10.0(v)

0.0

P112 FW

side

gain

0.0-200.0(%)

0.0

P113

RV side gain

0.0-200.0(%)

0.0

P114

Time constant of the filter

5.-500.(ms)

5.

Option

*X00x

Note: Parameters indicated with an asterisk and yellow highlight are affected by
setting of the frequency conversion function (parameter A074). See the function
description in Chapter 2. In addition to the parameters listed above, the following
parameters will also be scaled if this function is enabled:

D007 – Scaled Output Frequency Monitor
F001 – Output Frequency Setting

Advertising