Chapter 3 – parameter setting tables, Function mode – Hitachi SJ300 Series User Manual

Page 29

Advertising
background image

29

Chapter 3 – Parameter Setting Tables

Function mode

Code

Function name

Setting range

Initial data

remarks

b088

Resume on FRS cancellation
mode

00(0Hz start)/01(Start f-equaling)

00

b090

BRD usage ratio

0.0-100.0(%)

0.0

b091

Stop mode selection

00(deceleration stop)/01(Free-run stop)

00

b092

Cooling fan control

00(Always ON)/

01(ON during run, After power ON, then for 5 minutes on stop is implied.)

01

b095

BRD selection

00(invalid)/01(valid<invalid during stop>)/02(valid<valid during stop>)

00

b096

BRD ON level

330-380/660-760(V)

360/720

b098

Thermistor selection

00(invalid)/01(Positive temperature coefficient enable)/02 (NTC enable)

00

b099

Thermistor error level

0. – 9999. (ohm)

3000.

b120

Braking control selection

00(Invalid)/01(valid)

01

b121

Waiting time for releasing
braking conformation

0.00-5.00(s) 0.10

b122

Waiting time for acceleration

0.00-5.00(s)

0.40

b123

Waiting time for stop

0.00-5.00(s)

0.40

b124

Waiting time for signal
conformation

0.00-5.00(s) 0.00

*b125 Releasing

frequency

0.00-99.99/100.0-400.0(Hz)

0.00

b126

Releasing current

0.00*rated current-2.00*rated current(A)

0.10* rated

current of

inverter

*b127 Brake

OFF

frequency

0.00-400.00Hz

0.00

b128

Delay time at brake signal is
turned OFF

0.00-5.00s

0.50

C091

Debug mode selection

00(No display)/01(Display)

00

C102 Reset

selection

00(Trip cancel during ON)/01(Trip cancel during OFF)/

02(Valid only during trip<Cancel during ON>)

00

C111

Overload advance notice level

0.0-2.0*rated current(A)

Inverter rated

current

C121

O zero adjustment

0.-9999./1000-6553(10000-65530)

Set on

forwarding

C122

OI zero adjustment

0.-9999./1000-6553(10000-65530)

Set on

forwarding

C123

O2 zero adjustment

0.-9999./1000-6553(10000-65530)

Set on

forwarding

H001 Autotuning

selection

00(Invalid)/01(Valid(the motor does not rotate))/

02(Valid(the motor rotates))

00

H002 1

st

motor constant selection

00(Hitachi general purpose motor data)/01(Autotuning data)/

02(Autotuning data with online autotuning)

00

H003 1

st

allowable motor selection

0.20-75.0(kW) <0.2-160kW>

Set on

forwarding

H004 1

st

motor pole selection

2/4/6/8(pole)

4

H005 1

st

speed response setting

0.001-9.999/10.00-65.53

4.00

H006 1

st

stabilized factor

0. - 255.

100.

H020 1

st

motor constant R1

0.000-9.999/10.00-65.53(ohm)

Set on

forwarding

H021 1

st

motor constant R2

0.000-9.999/10.00-65.53(ohm)

Set on

forwarding

H022 1

st

motor constant L

0.00-99.99/100.0-655.3(mH)

Set on

forwarding

H023 1

st

motor constant I0

0.00-99.99/100.0-655.3(A)

Set on

forwarding

H024 1

st

motor constant J

0.001-9.999/10.00-99.99/100.0-9999.(kgm

2

)

Set on

forwarding

H030

1

st

motor constant R1

(Autotuning data)

0.000-9.999/10.00-65.53(ohm)

Set on

forwarding

H031

1

st

motor constant R2

(Autotuning data)

0.000-9.999/10.00-65.53(ohm)

Set on

forwarding

H032

1

st

motor constant L

(Autotuning data)

0.00-99.99/100.0-655.3(mH)

Set on

forwarding

H033

1

st

motor constant I0

(Autotuning data)

0.00-99.99/100.0-655.3(A)

Set on

forwarding

H034 1

st

motor constant J

0.001-9.999/10.00-99.99/100.0-9999.(kgm

2

)

Set on

forwarding

H050

1

st

PI-control proportion gain

setting

0.00-99.99/100.0-999.9/1000.(%) 100.0

H051

1

st

PI-control integration gain

setting

0.00-99.99/100.0-999.9/1000.(%) 100.0

H052

1

st

P-control proportion gain

setting

0.01-10.00 1.00

H060 1

st

0Hz-SLV limiter setting

0.-100.(%)

100.

H070

PI-control proportion gain for
switching

0.00-99.99/100.0-999.9/1000.(%) 100.0

H071

PI-control integration gain for
switching

0.00-99.99/100.0-999.9/1000.(%) 100.0

H072

P-control proportion gain for
switching

0.00-10.00 1.00

Miscel

laneou

s

Mot

o

r C

o

n

s

ta

nt

s

Advertising