Appendix A - Auto-tuning Procedure

43

Auto-tuning of Motor Constants

The SJ300 inverter features auto-tuning, which detects and records the motor characteristic
parameters to use in all vector control modes. Auto-tuning determines the resistance and
inductance of motor windings. Therefore, the motor must be connected to the inverter for this
procedure. Note that the auto-tuning feature is not associated with PID loop operation, which is
common on some control devices. The auto-tuning procedure must be conducted while the
inverter is stopped (not in Run mode), so it can use special output pulses to detect motor
characteristics. When using the inverter in sensorless vector control, sensorless vector control -
0Hz domain, or vector control with encoder feedback, the motor circuit constants are important. If
they are unknown, then you must first conduct the auto-tuning procedure. The inverter will
determine the constants and write new values for the related “H” Group settings. The auto-tuning
procedure requires that the inverter be configured to operate the 1st motor (do not set the
inverter to use 2nd and 3rd motor data during an auto-tuning procedure).

Function

Code

Name

Range

Notes

00 Disabled

01 Enabled,

without motor rotation (STATIC)

H001

Auto-tuning
Enable Setting

02 Enabled,

with motor rotation (DYNAMIC)

00

Inverter uses default TYPICAL motor parameters

01

Inverter uses Auto-tuning motor parameters

H002

Motor data
selection, 1st
motor

02

Adaptive tuning parameters

H003

Motor capacity,
1st motor

0.2 – 75, 0.2 – 160

Units: kW

H004

Motor poles
setting

2 / 4 / 6 / 8

Units: poles

H030

Auto-tuned motor
constant R1

Set automatically

Units: ohms

H031

Auto-tuned motor
constant R2

Set automatically

Units: ohms

H032

Auto-tuned motor
constant L

Set automatically

Units: mH

H033

Auto-tuned motor
constant Io

Set automatically

Units: A

H034

Auto-tuned motor
constant J

Set automatically

Units: kgm

2

A003

Base frequency
setting

30 to maximum freq. Units: Hz

00

Disabled (Disable during auto-tuning)

A051

DC braking
enable

01 Enabled

200/215/220/230/240

Valid setting choices for 200V class
inverters

A082

AVR voltage
select

380/400/415/440/ 460/480

Valid setting choices for 400V class
inverters