Hitachi SJ300 Series User Manual

Page 35

Advertising
background image

Chapter 4

Adjustment

Input the inductance phase based on a Y-connection. Motor constants for a delta
connection should be converted being divided by

3

.

8. Motor no-load (excitation) current I

0

(H023 or H033)

Input excitation or no-load current. This can be obtained from motor specification
sheets provided by the manufacturer. If safe and feasible, it can also be measured
using a current clamp by running the motor with no load at base speed.

9. Motor inertia J (H024 or H034)

In the beginning, input approximately 6 times the inertia value of motor itself. For
further adjustment, refer to

Section 4.4

.