Venting installation – FMI PFS DVF42NH-HA User Manual

Page 14

Advertising
background image

www.fmiproducts.com

125078-01B

14

Flat Ceiling Installation

1. Cut a 11

1

/

2

" square hole in ceiling using

locating hole as a center point. Opening

should be framed to 11

1

/

2

" x 11

1

/

2

" inside

dimensions, as shown in Figure 8 on page

9 using framing lumber the same size as

ceiling joists. If area above ceiling is an

insulated ceiling or an attic, nail firestop

from top side. This prevents loose insula-

tion from falling into required clearance

space. If area above ceiling is a living

space, install firestop below framed hole.

Firestop should be installed with no less

than three nails per side (see Figure 15).

2. Assemble desired lengths of pipe and

elbows necessary to reach from fireplace

flue up through firestop. Be sure all pipe

and elbow connections are fully twist-

locked (see Figure 8, page 11).

3. Cut a hole in the roof using locating hole

as a center point. (Cover any exposed

venting inStALLAtiOn

Continued

Figure 15 - Offset with Wall Strap and 45°

Elbows

45° Elbow

Wall Strap

Roof Flashing

Ceiling Firestop

open vent pipes before cutting hole in

roof.) The 11

1

/

2

" x 11

1

/

2

" hole must be

measured on the horizontal; actual length

may be larger depending on pitch of roof.

There must be a 1" clearance from vent

pipe to combustible materials. Frame

opening as shown in Figure 9, page 11.

4. Connect a section of pipe and extend up

through hole.

Note: If an offset is needed to avoid

obstructions, you must support vent pipe

every 3 feet. Use wall straps for this pur-

pose (see Figure 15). Whenever possible,

use 45° elbows instead of 90° elbows. The

45° elbow offers less restriction to the flow

of flue gases.

5. Place flashing over pipe section(s) ex-

tending through roof. Secure base of

flashing to roof and framing with roofing

nails. Be sure roofing material overlaps

top edge of flashing as shown in Figure

15. There must be a 1" clearance from

vent pipe to combustible materials.

6. Continue to add pipe sections until height

of vent cap meets the minimum building

code requirements described in Figure 7

on page 8.

Note: You must increase vent height for

steep roof pitches. Nearby trees, adjoining

rooflines, steep pitched roofs and other

similar factors may cause poor draft or

down-drafting in high winds. Increasing

vent height may solve this problem.

7. Twist-lock vent cap onto last section of

vent pipe.

2. Set fireplace in desired location. Drop a

plumb line down from ceiling to position

of fireplace exit flue. Mark center point

where vent will penetrate ceiling. Drill a

small locating hole at this point.

3. Drop a plumb line from inside of roof to

locating hole in ceiling. Mark center point

where vent will penetrate roof. Drill a small

locating hole at this point.

Vent Termination Chart

Minimum Height

Roof pitch

Feet Min.

Flat to 6/12

1

6/12 to 7/12

1.25

Over 7/12 to 8/12

1.5

Over 8/12 to 9/12

2

Over 9/12 to 10/12

2.5

Over 10/12 to 11/12

3.25

Over 11/12 to 12/12

4

Over 12/12 to 14/12

5

Over 14/12 to 16/12

6

Over 16/12 to 18/12

7

Over 18/12 to 20/12

7.5

Over 20/12 to 21/12

8.0

Advertising