Specifications

Electrical Measurements

21

21-5

Voltage Interrupts

Settings Adjustment

Range

Resolution

Additional

Information

Interrupt Threshold level 0.0 ... 50.0 % of Vnom

0.1 %

Interrupt Hysteresis level 0.0 ... 10.0 % of Vnom

0.1 %

results based on ½ cycle
rms

Measurements Measurement

Range Resolution

Accuracy

Interrupt Magnitude

0.0 % ... 100.0 % of
Vnom

0.1 %

± 1 % of Vnom

Interrupt Duration

hhh:mm:ss:mmm

10 ms

± 20 ms (at F= 50 Hz)


Voltage Unbalance

Measurements Measurement

Range Resolution

Accuracy

Negative Unbalance
Ratio

0.0 ... 5.0 %

0.1 %

± 0.5 %

Zero Unbalance Ratio

0.0 ... 5.0 %

0.1 %

± 0.5 %


Rapid Voltage Changes

Settings Adjustment

Range

Resolution

Additional

Information

Steady Voltage
Tolerance

0.0 ... 10.0 % of Vnom

0.1 %

Minimum Steady Time

0.0 ... 10.0 s

0.1 s

Minimum Voltage
Difference

0.0 ... 10.0 % of Vnom

0.1 %

Minimum Rate of
Change

0.0 ... 10.0 %/s of Vnom 0.1 %/s

results based on ½ cycle
rms

Measurements Measurement

Range Resolution

Accuracy

Steady Voltage
Difference

0.0 ... 100.0 % of Vnom

0.1 %

± 1 % of Vnom


Transient Voltages

Settings Range

Additional

Information

Transient Capture
Threshold

0 ... 999 % of Vnom

Percentual deviation from the repetitive waveform

Advertising