Tips and hints – Fluke 434 User Manual

Page 50

Advertising
background image

Fluke 433/434

Users Manual

11-4

PREFerences. With the demand interval set to OFF the Trend functions as usual with

automatic horizontal scaling.
Available function keys:

F1

Assign up/down arrow keys to select a row from the table
for Trend display. The selected row is displayed in the
screen header.

F2

Cursor on/off.

F3

Assign the arrow keys to Cursor or Zoom operation.

F4

Return to table screen.

F5

Switch between HOLD and RUN of screen update.
Switching from HOLD to RUN invokes a menu to select
immediate (NOW) or TIMED start time which allows you
to define start and duration of the measurement.

Cursor. When the Cursor is on, the Trend values at the Cursor are displayed in the screen

header. Moving the Cursor off the left or right side of the screen brings the next of six

screens into the viewing area.
Zoom. Allows you to expand or shrink the display vertically or horizontally to view

details or to fit a complete graph within the screen area. Zoom and Cursor are operated by

the arrow keys and explained in Chapter 17.
Offset and Span are preset for a good display in most cases. This is based upon Nominal

Voltage (Vnom) and Current range (A range). If desired, you can adjust Offset and Span.

The adjustment menu is reached via the SETUP key and function key F3 - FUNCTION

PREF. See Chapter 18, FUNCTION PREFerences.

Tips and Hints

Power mode can be used to record apparent power (kVA) of a transformer over several

hours. Look at the Trend and find out if there are times that the transformer is overloaded.

You can transfer loads to other transformers, stagger the timing of loads, or if necessary

replace the transformer with a larger one.
Interpretation of Power Factor when measured at a device:
• PF = 0 to 1: not all supplied power is consumed, a certain amount of reactive power

is present. Current leads (capacitive load) or lags (inductive load).

• PF = 1: all supplied power is consumed by the device. Voltage and current are in

phase.

• PF = -1: device generates power. Current and voltage are in phase.
• PF = -1 to 0: device is generating power. Current leads or lags.
If you see negative power or power factor readings and you are connected to a load,

check to make sure the arrows on your current clamps are pointing towards the load.
Reactive power (VAR) is most often due to inductive loads such as motors, inductors,

and transformers. Installation of correction capacitors can correct for inductive VAR’s.

Be sure to check with a qualified engineer before adding PF-correction capacitors,

especially if you measure current harmonics in your system.

Advertising
This manual is related to the following products:

433