Application of wiring and equipment, Fvr-c9s-7ux caution – GE FVR-C9S-7UX User Manual

Page 16

Advertising
background image

16

FVR-C9S-7UX

CAUTION:

The control circuit terminal wiring should be
kept as far as possible from the main circuit
wiring to prevent operational error due to
noise interference. Never install them in the
same duct or conduit. (A separation distance
of 4 inches [10cm] or more is recom-
mended.) If the control circuit wiring must
cross the main circuit wiring, make sure it
crosses at a right angle.

Use shielded, twisted wire for the control
circuit wiring , which should be as short as
possible (65 feet [20m] or less).

Install a surge absorber in parallel with any
magnet contactors, solenoids, relays or
timer coils, which are close to the drive.

Applicable motor output [Hp]

1/8

1/4

1/2

1

2

Drive type

FVRF12

FVRF25

FVRF50

FVRF001 FVRF002

C9S-7UX C9S-7UX C9S-7UX C9S-7UX C9S-7UX

Output rated capacity [kVA]

0.27

0.5

0.87

1.5

2.7

Applicable wire size

Main circuit

14

12

(AWG)

Contol circuit

24

MCCB

6

10

16

20

ELCB

6

10

16

20

Listed fuse*

20

30

* The use of quick-acting fuses is required to validate UL listing. The factory

C92-7-15

recommendation is Bussman type JKS or equivalent.

Long wiring lengths between the motor and
the drive will result in increased capacitance
and leakage current. This may cause earlier
activation of such protective functions as:
overcurrent protection, overheating protec-
tion and electronic thermal overload, or the
error in current detection may become large.
To avoid these, adjust the length of wiring
between the drive and the motor so that is
does not exceed the length shown below.

FVRF12C9S-7UX : 165 feet (50m)
FVRF25 to 002C9S-7UX : 325 feet (100m)

9. Application of Wiring and Equipment