Fvr-c9s-7ux – GE FVR-C9S-7UX User Manual

Page 23

Advertising
background image

23

FVR-C9S-7UX

Function Code Tables

Function

Code

Function

Date Code Range

Unit

Min.

Set.

Factory

Setting

Change

During

Operation

F00

Data protection

0: Data change possible
1: Data change not possible

0

No

F01

Frequency
Command

0: Keypad panel (UP/DOWN keys)
1: Analog input (VR, DC0 - 10V or DC4 - 20mA)

1

No

F02

Operation
Command

0: Keypad panel operation (RUN/STOP keys)
1: External signal operation (FWD/REV terminals)

0

No

F03

Maximum
Frequency

50 - 120 Hz

Hz

1

60 Hz

No

F04

Base Frequency

50 - 120 Hz

Hz

1

60 Hz

No

F05

Acceleration TIme

0.0 - 60s (0.0 setting = 0.01s)

s

0.1

6.0s

Yes

F06

Deceleration Time

0.0 - 60s (0.0 setting = 0.01s)

s

0.1

6.0s

Yes

F07

Torque Boost

0 - 31 (code)

13

Yes

F08

Electronic Thermal
Overload Relay
Operation

0: Inactive
1: Active (standard 4-pole motor)
2: Active (forced-air cooled motor)

0

No

F09

Electronic Thermal
Overload Relay
Level

30 - 105% of rated current of drive

%

1

100%

No

F10

Restart after
Momentary Power
Failure

0: Inactive
1: Active (Restart drive in 0.5s after power failure)

0

No

F11

Gain for Frequency
Setting Signal

0: For 0 - 10 V
1: For 0 - 5 V

0

No

F12

DC Brake (Level
Setting)

0 - 100%

1

50%

Yes

F13

DC Brake (Time)

0.0 (inactive) 0.1 - 30s

s

0.1

0.1s

Yes

F14

Starting Frequency 1 - 6 Hz

Hz

1

1 Hz

No

C92-01