Fvr-c9s-7ux, F 0 7 torque boost, F 0 8 electronic thermal overload relay – GE FVR-C9S-7UX User Manual

Page 26: F 0 9 electronic thermal overload relay level

Advertising
background image

26

FVR-C9S-7UX

F 0 7 Torque Boost

Can be set from among 32 different levels in accordance with the type of load, the

characteristics of the motor, etc.

0

1

2 Low

3

1 High

8 Set to match this when using a Fuji FV motor designed for use with a drive.

F 0 8 Electronic Thermal Overload Relay

Either of the following two can be selected.

0 Inactive

1 Active (electronic thermal overload relay protection) For a standard 4-pole motor

2 Active (electronic thermal overload relay protection) For a Fuji FV motor

F 0 9 Electronic Thermal Overload Relay Level

Sets the operation level for the electronic thermal overload relay.

3

0 Setting range: 30 to 105% (increments of 1%)

1

0

5

Motor's rated current

Setting value (%) = K X

X 100

Drive's rated current

For a reduced torque load (fan, pump, etc.)

Drive Capacity

Wiring Length : feet

F12C9S-7UX

K = 1.2

External thermal OL relay is recommended

F25C9S-7UX

K = 1

K = 1.1

K = 1.2

F50C9S-7UX

K = 1

K = 1.1

001C9S-7UX

K = 1

002C9S-7UX

C97-10

0

1 3 0

1 6 5

3 2 5

6 5 5

Output frequency f

Output
voltage

High

Low

Advertising