Fvr-c9s-7ux, F 2 4 high limiter f 2 5 low limiter, F 2 6 bias frequency – GE FVR-C9S-7UX User Manual

Page 31: F 2 7 thr terminal function, F 2 8 bx terminal function

Advertising
background image

31

FVR-C9S-7UX

F 2 4 High Limiter
F 2 5 Low Limiter

The upper and lower and lower limits of the output frequency can be set.

0 Set as a percentage of the maximum frequency in increments of 1% within a range of 0 to 100%

1

0

0

If the value set for low limiter is higher than that set for the
high limiter, the high limiter will take priority and the low
limiter will be ignored. Thus, operation will always be in
accordance with the high limiter value regardless of the
frequency setting.

F 2 6 Bias Frequency

Outputs a bias frequency with respect to the analog frequency setting.

0 Set as a percentage of the maximum frequency in increments of 1% within a range of 0 to 100%

1

0

0

F 2 7 THR Terminal Function

This function enables terminal THR to be used for two different functions by changing the data
code as follows:

0 External alarm input
1 Multistep speed selection (X1)

This function data cannot be changed during operation. (Possible to change only in STOP mode).

F 2 8 BX Terminal Function

This function enables terminal BX to be used for two different functions by changing the data code as follows:

0 Motor coast-to-stop command input
1 Multistep speed selection (X2)

This function data cannot be changed during operation. (Possible to change only in STOP mode).

100%

100%

High
limiter

Output
frequency

Low limiter

Frequency
setting

100%

100%

Output
frequency

Frequency
setting

Bias

Advertising