Terminal function explanation cont, Fvr-c9s-7ux – GE FVR-C9S-7UX User Manual

Page 18

Advertising
background image

18

FVR-C9S-7UX

Terminal Function Explanation

Classi-

fication

Terminal Code

Terminal Name

Explanation of Function

Output for

Motor

FM

Analog Monitor

Outputs + 10VDC between FM and CM terminals. When
frquency setting is equal to the maximum frequency setting,
outputs + 10VDC at 150% current when monitoring output
current.

• Two DC voltmeters (internal resistance of 10K ohm or
greater) can be connected.

• In case of DC ammeter (1mA full scale), it is necessary to
add series resistance of 10K ohm (1/2W)

• This output is a pulse output constant frequency (38. 1 Hz)
which has a variable duty.

Contact

Output

30A, B, C

Combined Alarm Output
Terminals

Output via no volt signal (contact1c) to indicate that the
drive's protective function has been activated by an alarm.

• Contact capacity (DC48V. 0.3A)

C92-04

Terminal Function Explanation cont.