FVR-C9S-7UX

6) It is important that all lead length are kept
as short as possible and that incoming
mains and outgoing motor cables are kept
well separated.

7) Segregate power cables from control
wiring as possible as you can, and avoid
parallel cable runs to minimize “noise cou-
pling”. Wherever runs of power and control
cable must cross, try to achieve this at right
angles.

8) FVR drives should be installed, and are
designed to operate, within an electrically
shielded metal enclosure.

The RFI filters range are designed especially
for the FVR drive and help to ensure EMC
compliance of machinery an installations
using the drives. The drives may be mounted
on top of the filter using the integral fixing
positions, the intention being that valuable
space inside wiring cabinets may be saved.
(Refer to Fig. 1 and Table 1)


Filter

Applied

Rated

Max Rated

Dimensions inches

Drive

Sub

Part No.

Drive

Current

Voltage

L x W x H

X

Y

Fixings

Filters

EFL-0.2C9-7

FVRF12C9S-7UX

3A

6.69 x 3.35 x 1.38 1.97

6.1

M4 0.16

Ferrite

FVRF25C9S-7UX

x0.63 (2pcs.)

OC1x (1 pcs.)

EFL-0.75C9-7

FVRF50C9S-7UX

10A

1-Phase

6.69 x 3.35 x 1.38 1.97 6.10

M4 0.16

FVR001C9S-7UX

240 VAC

x0.63 (2 pcs.)

EFL-2.2C9-7

FVR002C9S-7UX

16A

7.09 x 4.53 x 1.38 3.50 6.50

M4 0.16

Ferrite

x0.63 (4 pcs.)

OC2x (1 pcs.)

7-'006

Mains input
terminals

Earth Stud

Drive fixing
positions

Earth Stud

Load terminals
to drive
input

Y

X

W

L

N

LINE

LOAD

L’

N’

L

H

Fig. 1 RFI Filters

Table 1 RFI Filter Dimensions Conforms to EN55011 Class B