3.4 UPS PARALLELED ON THE SAME BATTERY

NOTE !

A parallel system with a Common Battery for two or more UPS, requires a particular
installation and adequate setting of some parameters, (accessible only through

password), and can therefore only be done by a qualified GE engineer.

Usually each UPS Unit runs with its own Battery.

In case of parallel units running with a Common Battery (max. 4 UPS - see Fig. 3.4-1), the sharing circuit
between the individual UPS is integrated in the communication bus of the system in order to assure an

equal sharing of the Rectifiers output currents.

Fig. 3.4-1 Diagram RPA system with UPS on common battery

1 –

2 –

3 –


4 –

5 –

6 –


7 –


8 –

Rectifier

Inverter

Automatic Bypass


Manual Bypass

Mains Power

Load Bus Bar


External Battery Fuse


Battery


Pay attention to the following recommendations:

The units delivered for this functioning mode needs a special parameters setting, so they must be
prepared in advance before the installation.

The installation must be performed only with the UPS system completely shut down.

The AC Rectifiers input power (5) must be the same, with clockwise phase rotation for each unit.

Each Rectifier must be set for the same floating DC voltage and the same Battery current limitation.

It is mandatory to install the fuses / MCB (7) on each line connecting the Rectifiers to the common
Battery for maintenance / safety reasons (see Section 4.7.2).

In case a unit must be powered down for maintenance, switch-OFF the concerned unit before open
the DC fuses / MCB on the Battery line (7).

If an emergency generator set supplies the UPS, and the free contact “Generator ON” is connected

to the Customer Interface, connect a separate NO free contact on each parallel unit.

Do not connect the temperature sensor for automatic battery floating voltage compensation.

Do not enable the function Boost charge.