Operating Manual LP 33 Series 30 & 40 kVA

3. Switch On the output switch Q1 (Pos. I).

The output will be supplied by the mains through the bypass.

LP 33 40kVA

APPLICAT. ON UTILITY

= 70%

Verify, selecting the screen METERING/Udcp and Udcn, that the
booster voltage has reached about 215 VDC.

Udcp=215V Udcn=215V
Ubp=164V Ubn=164V

F

Charge level

= 100%

Autonomy =

800min

4. Switch On the inverter entering the screen:

MENU/COMMAND MENU/INVERTER ON

COMMAND MENU

INVERTER ON *
INVERTER OFF

Some seconds later the load will be transferred on inverter
and the main screen will display: APPLICATION ON UPS

LP 33 40kVA

APPLICATION ON UPS

= 70%

5. Operation mode selection.

LP 33 Series is delivered normally selected for permanent VFI operation.
ECO Mode can be enabled and the ECO START time & ECO STOP time can be programmed for each
day of the week (see Section 6.3.1-5).

END OF PROCEDURE



NOTE !

Even if the UPS is delivered with the battery fully charged, they could be partially

discharged during transportation or storage.
It is recommended to recharge the battery during a few hours in order to provide the
complete battery
energy stored to the load in the event of mains failure.