Operating Manual LP 33 Series 30 & 40 kVA

Code

Alarm

Meaning

4118

BATTERY

FAULT

During battery test the DC voltage falls under the critical
level.

If the boost voltage has not been reached within 24 hours,

then the charge voltage returns to floating voltage.
Battery test is stopped.

4130

TURN ON RECT.

OR SHUTDOWN UPS

Rectifier and inverter are OFF.
The DC power supply is discharging the battery slowly.

Rectifier must be restarted or battery must be disconnected
in order to avoid damages.

4140

RECTIFIER

CONTROL FAILURE

Rectifier voltage hasn’t reached the set value.

Probably fault on regulation loop.
The DC capacitors are not equally charged (more of 50 VDC

of difference).
The rectifier is switched OFF.

4301

INVERTER

FUSES FAILURE

Inverter output fuses blown.
Signaled by electronic detector.

Inverter can be started manually after replacement of fuses.

4304

K7 CLOSING

FAILURE

K7 not closed despite a closing command being done.
Signaled by auxiliary contact.

Load will be supplied by mains.

4305

K7 OPENING

FAILURE

K7 not open despite an opening command being done.
Signaled by auxiliary contact.

Load will be supplied by mains.

4312

INV. VOLTAGE

OUT OF TOLERANCE

Inverter output voltage is out of the tolerances defined in
respective parameter (±10%).

Inverter is switched OFF.

4320

ISMAX

DETECTION

Detection of inverter bridge (Is) current limitation cause
inverter OFF and automatic restart (message 320).

After 3 times inverter switches OFF for persistent Is max
detection in time.

Inverter switch OFF, and it can be restarted manually.

4340

INVERTER

CONTROL FAILURE

The slave oscillator is not synchronized with the master, thus
causing the shutdown of it’s inverter.

4347

OSCILLATOR

FAILURE

Auto calibration of the Inverters free-run frequency was not
possible.
The oscillator frequency of this unit is out of tolerance.

4402

RECTIFIER

CANNOT BE TURNED ON

The rectifier cannot be turned on because the DC link
voltage has not reached the requested value.

4404

K6 CLOSING

FAILURE

K6 not closed despite a closing command being done.

Signaled by auxiliary contact.
The load cannot be supplied by electronic bypass.

4405

K6 OPENING

FAILURE

K6 not open despite an opening command being done.
Signaled by auxiliary contact.

4410

BYPASS MAINS

OUT OF TOLERANCE

The mains bypass voltage is out of the tolerances (±10%).
K6 opens, synchronization with mains is inhibited and

transfer to mains is blocked.